13. Troubleshooting

Problem

Possible Cause

Corrective Action

Unit will not turn ON 

ON/TEST button not pushed or

Press the ON/TEST button for more than 2
seconds to power the UPS and load. 

not pushed long enough.

Fuse is blown or the
circuit breaker has tripped.

V

Output short circuit, or UPS is 
overloaded.

ery low or no utility voltage.

Check 

To remove short circuited equipment or
overload, disconnect connected equipment
then re-set the circuit breaker.

the AC power supply to the UPS. 

UPS will not turn ON or OFF

Computer interface or accessory 

Disconnect the computer interface or 

problem. ON/TEST or OFF button 

accessory. If the UPS then functions  

not pushed long enough.

normally, check the interface cable, the
attached computer and/or the accessory.

UPS operates on battery even 

UPS’s input circuit breaker tripped, or

input fuse is blown.

Remove connected loads from the UPS by

though line voltage is apparently 

unplugging equipment and reset the circuit

breaker.

Remove connected loads from the UPS by
unplugging equipment and reset the circuit

breaker.

present

UPS beeps slowly

Normal UPS operation.

None – the UPS is supporting the load.

UPS

Front panel indicators flash
sequentially (LED models) 

All indicators are flashing and
UPS emits a constant tone 

UPS operates normally, but the 
site wiring fault indicator is on.

does not provide expected

The UPS's battery is not fully recharged
due to recient use or it is near the end 
of its service life. 

Charge the battery. If the battery is near  

back-up time 

the end of its service life, consider replacing
it, even if the fault code "E07" has not been
displayed yet.

The

The UPS has shut down by remote
control.

Internal UPS fault.

Building wire error - e.g. missing Ground
or Hot and Neutral wires are reversed.

UPS is overloaded.

Check 

None - The UPS will restart automatically
when the utility power returns if configured
to do so, or manually turned on.

Do not attempt to use the UPS. Turn it off,
power it down and have it serviced.

Have a qualified electrician correct the 
building wiring.

Low battery light is ON and all
LED's are OFF

The UPS has shut down and the battery
has been discharged or depleted.

None - The UPS will return to normal 
operation when the utility power is restored
and the battery is sufficently recharged.

Replace battery light is ON

Faulty batteries.

The batteries may need to be recharged 
for at least 4 hours. Should the problem
persist - replace with new batteries.

the UPS’s load display and remove

noncritical loads.

13. Troubleshooting

 18

Summary of Contents for Track Series

Page 1: ...USER MANUAL Track Series Line Interactive True Sine Wave Output Uninterruptible Power Supply...

Page 2: ......

Page 3: ..._____________________________ Please take the time to read this manual It provides safety installation and operating instructions that will allow you to derive the maximum performance and service life...

Page 4: ...s a Remove watches rings and other jewelry or metal objects b Use only tools with insulated handles c Wear rubber gloves and boots d Do not lay tools or metal parts on top of batteries e Disconnect ch...

Page 5: ...unctionality 2 4 Installation 8 5 Operation 13 6 Alarms 14 7 Software Options 14 8 Care Maintenance 15 9 Computer Interface Port 15 10 Battery Replacement 16 11 Storage 17 12 Fault Codes 17 13 Trouble...

Page 6: ...reduce the risk of electric shock disconnect the UPS from the main AC supply before installing any interface cables Reconnect the power cord only after the signaling interconnections have been made Th...

Page 7: ...f battery capacity It also displays utility line voltage 3 4 LOAD Bar Graph This LED display shows the power being drawn by the load 3 5 BUCK AVR Indicator YELLOW LED This LED illuminates when the UPS...

Page 8: ...lity line voltage displays 3 12 OFF Button Pressing this button turns OFF the UPS and its connected loads 3 13 SELECT Button Depressing and holding the select button cycles through various LCD display...

Page 9: ...ry in 20 increments 3 20 LOAD LEVEL BAR GRAPH This graph shows how much of the units available capacity is being utilized in 20 increments 3 21 INPUT I P OR OUTPUT O P VOLTAGE Vac Pressing the SELECT...

Page 10: ...INPUT FUSE OUTPUT IN OUT STANDARD 600VA RM MODEL REMOTE PORT IN OUT CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER 3 25 3 29 3 27 EXTENDED RUN TIME RACK MOUNT 3000VA MODEL EXTENDED R...

Page 11: ...ANEL 600 3000VA RM 2U LCD FRONT PANEL 600 3000VA RM 2U REAR VIEW 600 1000VA RM 2U REAR VIEW 1500VA RM 2U REAR VIEW 2000VA RM 2U REAR VIEW 2500 3000VA RM 2U 3 Functionality Front Rear Views 19 Rack Mou...

Page 12: ...e protected receptacle s capacity CAUTION Replace only with same fuse type and rating 3 30 SITE WIRING FAULT INDICATORS RED LED Some Models This LED illuminates when the UPS is connected to an imprope...

Page 13: ...nd the device to be protected telephone modem etc is plugged into the connector labeled OUT NOTE This surge protection device is for indoor use only Never install telephone wiring during a lightning s...

Page 14: ...ery Pack Connection Extended Run Time Models Before connecting ensure that the external battery pack and connector cable are compatible with the UPS Use only the factory supplied external battery conn...

Page 15: ...l Mount Installation The following diagrams illustrate how to install or mount the UPS and battery packs when applicable in either vertical or wall mount applications Vertical Installation Wall mount...

Page 16: ...Mount Installation The following diagrams illustrate how to install or mount the UPS and battery packs when applicable in 19 rack mount applications Lower Slide Rail Installation Rear Bracket Installa...

Page 17: ...Unit Stack Installation The following diagrams illustrate how to stack the units and battery packs when applicable Stacking Units 12...

Page 18: ...the UPS s rated capacity being utilized For example if two LEDs or segments are illuminated the load is drawing between 20 and 40 of the UPS s rated capacity See section 3 for location of the display...

Page 19: ...ase refer to the back of the software CD envelope for installation instructions For operational instrucions install the software launch the program then click HELP in the upper left corner of the soft...

Page 20: ...to the communication port on the back of the UPS a special plug in card may be needed in the event one is not available Some computers may also need special software Contact tech support for details o...

Page 21: ...t the AC power cord from the UPS 3 Remove the two 2 front panel securing screws located on either side of the unit NOTE Some models Remove the two 2 lower front panel screws located on both sides of t...

Page 22: ...cables connected to the computer interface port to avoid draining the battery 11 2 Extended Storage During extended storage in environments where the ambient temperature is 5 to 86 F 15 to 30 C charge...

Page 23: ...anel indicators flash sequentially LED models All indicators are flashing and UPS emits a constant tone UPS operates normally but the site wiring fault indicator is on does not provide expected The UP...

Page 24: ...detection time Efficiency Standby Mode Greater than 95 Overload Capacity 110 for 20 seconds 125 for 5 seconds EXTENDED RUN TIME MODELS GENERAL Rated power 1000 VA 1500 VA 2000 VA 3000 VA with a power...

Page 25: ...e models 32 F to 104 F 0 C to 40 C All standard run time models 32 F to 77 F 0 C to 25 C 3000VA extended run time models Optimum temperature range 59 F to 77 F 15 C to 25 C Storage temperature 5 F to...

Page 26: ...acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Battery Quantity Backup time full load 9 min 5 min 5 min 5 min Recharge time 8 hours to 90 Dimensions i...

Page 27: ...x 480 x 430 6 7 x 21 6 x 16 9 170 x 550 x 430 Weight lbs kg net 50 22 7 90 41 110 50 125 57 Extended Run Time 19 Rack mount Models Capacity Input Connection Fixed power cord Hardwire terminals Output...

Page 28: ...are intended to limit the maximum amplitude of transient voltage surges on power lines to specified values They are not intended to function as surge arrestors The UPS is intended to be installed on t...

Page 29: ...__________________________________________________________ ______________________________________________________________________________ ______________________________________________________________...

Page 30: ......

Page 31: ......

Page 32: ...trackuserman2007rev2 Marathon Power Inc 2007 www marathon power com...

Reviews: