Connect the cable from the batteries to the
48V BATTERY CONNECTOR
into the
TRTC-2002-N1.
Each of the six contacts are of form C type, meaning Normally Open (NO), common (C) and
Normally Closed (NC) dry contact rated for 1A @ 240VAC. Each of these contacts can be
individually programmed to energize and stay latched for ON BATTERY, LOW BATTERY,
TIMER, ALARM, FAULT and many other conditions as described in subsequent chapters.
The ON BATTERY contact(s) are activated as soon as the unit is transferred to Battery
mode. LOW BATTERY contact(s) are activated only in the Battery mode, as soon as the
discharged battery reaches the lower value battery capacity as set by user and remains
latched as long as the system remains in Battery mode.
The TIMER contact(s) are activated only in the Battery mode after the user-programmed
time is attained, that can be set in 15 minute intervals from 15 minutes to 8 hours.
Torque status/self-test terminal block to a maximum of 4.4 lb.-in (0.5Nm).
Maximum wire size 14 AWG
.
Connect the
COMMUNICATION CABLES
where appropriate.
USB
SERIAL
MODEM
ETHERNET EXT