5.
4
Operating Modes
Purpose:
Describes the operating modes.
The LCD automatically displays the following modes when they change.
LCD Shows
Explanation
STANBY
This mode is displayed when the unit is first turned on. The
inverter remains off and the TRTC-2002-N1 does not provide
output power to the loads. If input line power is qualified, it
automatically switches to line mode. To provide battery to the
loads, use the manual on function (see Section 5.7 Control).
ON LINE
The normal operating mode. Input line power is provided to the
loads the batteries are charging and the TRTC-2002-N1 is ready
to provide backup power.
BOOST
The unit automatically transfers to BOOST mode to raise the
lower input line voltage when output drops below the user
programmable preset limit.
ON BATT
The unit automatically transfers to battery when input line power
is unqualified or not present. The batteries provide power to the
loads.
BUCK*
The unit automatically transfers to BUCK mode to reduce the
higher input line voltage when output raises above the user
programmable preset limit.
SELF TEST
When “Self-Test” mode is active, the unit will enter “Battery
Mode” automatically to test or check if output voltage and
waveform is correct. After the programmed duration, the unit
returns back to “Line Mode”. Users may use “Maintenance
Mode” to configure a longer time for self-test. Default time for
self-test is 1 minute.
LOW BATT
When the unit is in “Battery Mode” the batteries begin to
discharge. If the battery voltage falls below the user programmed
(40% default setting) of its capacity. “Low Bat” warning appears.
*When enabled.
The following mode may be programmed by the User (see Section 5.8 Settings).
TIP:
35
Summary of Contents for TRTC-2002-N1
Page 1: ......
Page 2: ...2...
Page 45: ...6 2 Menu Tree 45...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48...
Page 76: ...HyperTerminal at a Glance 76...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ...2017 Marathon Power Inc TRTC 2002 N1 User Manual_Jan_2017 2017 Marathon Power Inc...