5.1
0
Fault Menu
Purpose:
Describes the Fault Submenu and how the use the LCD for troubleshooting.
Procedure:
When the red
ALARM LED is continuously
ON, the unit has a fault, indicating
a condition where backup power is unavailable. Press
ENTER
to display fault description.
When the unit has a fault and line power is qualified and available, the output loads
are directly connected to the Input line with no line conditioning or backup power
provided.
LCD SHOWS
FAULT
DESCRIPTION
Short Circuit
Short Circuit
The load is short-circuited or the inverter did not start.
Batt. Low Volt
Low Battery Voltage *
The batteries output voltage is low.
Batt. High Volt
High Battery Voltage *
The batteries output voltage is high.
Temp High
High Temperature *
The battery temperature or the TRTC-2002-N1 internal
temperature is high.
Over Load
Overload
The loads are drawing more power than the TRTC-2002-N1
can provide.
Fault Table
*These faults are self-resetting. After the fault condition is removed, the unit automatically
returns to Line mode if the line is qualified or Battery mode if not. For all other faults, the unit
is reset by shutting it down and restarting it using the AC and battery breakers. The faults
can also be reset in the Control Menu of the LCD display.
TIP:
42
Summary of Contents for TRTC-2002-N1
Page 1: ......
Page 2: ...2...
Page 45: ...6 2 Menu Tree 45...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48...
Page 76: ...HyperTerminal at a Glance 76...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ...2017 Marathon Power Inc TRTC 2002 N1 User Manual_Jan_2017 2017 Marathon Power Inc...