EVT/TIMER
INV Event
00019
The numbers of Input Power Failures
INV Timer
0000 Hours 07 Minutes
Total time that the battery was discharged since the last RESET
BUCK Event
00000
The numbers of BUCK function active
BUCK Timer
0000 Hours 00 Minutes
Total time that the BUCK function since the last RESET
BOOST Event
00000
The numbers of BOOST function active
BOOST Timer
0000 Hours 00 Minutes
Total time that the BOOST function since the last RESET
6.8 Maintenance
Menu 3 below lists the various maintenance options.
Procedure
: At the main menu, type 3 and press ENTER. The Maintenance Menu shown
below is displayed. To return to the main menu, press ENTER.
[ 3 - Maintenance ]
30 Battery Test Options
The start - stop for the Battery Test / Self-Test is initiated here.
The test duration is user programmable in 1 minute intervals
from 1 to 255 minutes. The factory default setting is 1 minute.
Tip: The time duration can be changed only when TRTC-
2002-N1 is in line mode.
31 Output Shutdown
This allows output to be switched OFF or Shutdown. TRTC-
2002-N1 switches to STANDBY mode when this option is
activated.
32 Inverter On/Off
During the BATTERY or STANDBY mode, this option allows
the inverter to be switched OFF or turned ON after the user
programmable delay time.
The delay can be user programmable in 0.5 seconds steps
from 0 to a maximum setting of 255 steps (128 seconds). The
delay is only available in Standby or Battery modes. When the
unit returns to Line Mode, the delay resets back to a default of
0 seconds.
Thus during a battery discharge or ON BATTERY mode,
operator can stop the inverter immediately after user.
33 Change Password *
This option allows for the change of password. The factory set
default password is 1111.
Tip: the password can only be changed in Line mode.
34 Line Qualify Time
When the input power returns and it is qualified, i.e. it is within
acceptable range, the transfer from Battery mode to Line
mode is delayed by user programmed 3 /10 / 30 seconds
herein that allows the returned utility power to settle down.
The factory set default value is 30 seconds.
35 Battery Voltage
Low Warning
The level for LOW BATTERY ALARM is set here. The
Voltage level is user programmable in 0.5VDC increments
from 42VDC to 55VDC. The factory default setting is 47.5VDC
54
Summary of Contents for TRTC-2002-N1
Page 1: ......
Page 2: ...2...
Page 45: ...6 2 Menu Tree 45...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48...
Page 76: ...HyperTerminal at a Glance 76...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ...2017 Marathon Power Inc TRTC 2002 N1 User Manual_Jan_2017 2017 Marathon Power Inc...