Section 8: Specifications
120V Versions
Rated Capacity and Power
1kVA / 700W
3kVA / 2100W
Input
Voltage and Tolerance
Single phase 120V, 80~160V at 70~100% load
70~160V at 50~70% load, 60~160V at 0~50% load
Frequency (Auto-sensing)
50Hz or 60Hz +/- 4Hz
Power Factor
0.97
Output
Voltage and Frequency
Single phase 120V +/- 2%, 50Hz or 60Hz +/-0.5% (Battery mode)
Transient Response
+/- 3% (100% load variation)
Waveform and Distortion
Sine wave, THD < 3% at 0-100% linear load
Overload Capacity
125~150% 30secs, switch to bypass and auto re-transfer; >150% for 200ms
Crest Ratio
3 : 1
Energy Storage
Capacity and Voltage
UltraCapacitor, 58F, 16V
Run-Time
15 seconds at full load, 40 seconds at half load
Recharge Time
Approx. 2 minutes (Input current dependent)
Life Cycle
Approximately 500,000 charge / discharge cycles
Bypass
Automatic
Upon overload and UPS failure
Voltage Range
88V ~ 126V +/-10V (adjustable via LCD panel)
Transfer Time
To and From Inverter
0 ms for AC fail; 2.5 ms typical to bypass
Audible Alarms
Battery Mode
4 second (adjustable), 1 second beep when capacity low
Overload
Beep twice per second
Fault
Continuous beep tone
Indicator
LCD
UPS status, I/P & O/P information, % Load, Event history
Communication
Serial Port
RS-232 Interface; Optional power monitoring software
SNMP Intelligent Slot
Network card with SNMP Manager and Web browser
Environment
Temperature
0-40 degrees C; 32-104 degrees F
Relative Humidity
0-95% non-condensing
Acoustic Noise (at 1M)
< 50 dBA
Physical
Electronics Module Weight
23 lbs / 10.5 kgs
23 lbs / 10.5 kgs
Energy Module Weight
34lbs. / 15.4 kgs
70 lbs / 32 kgs
Electronics Module Dims
17” x 3.3” x 18.3" / 440 x 88 x 465 mm 17” x 3.3” x 18.3" / 440 x 88 x 465 mm
Energy Module Dims
17” x 3.3” x 18.3" / 440 x 88 x 465 mm 17” x 6.6” x 18.3" / 440 x 176 x 465 mm
4
0