background image

 

2.0  Configuration and Modbus map 

 

User’s Manual GW-DLMS-232-ISK 

 

Page 10 

 

0.9.1 

4x40018 

4x40218 

LONG 

Time 

0.9.2 

4x40020 

4x40220 

LONG 

Date 

0.0.0 

4x40022 

4x40222 

LONG 

Address 

0.1.0 

4x40024 

4x40224 

FLOAT 

Billing period counter 

0.1.2* 

4x40026 

4x40226 

FLOAT 

Time stamp of the billing period 

1.4.0 

4x40028 

4x40228 

FLOAT 

Sum Li Active power+ (QI+QIV) 

2.4.0 

4x40030 

4x40230 

FLOAT 

Sum Li Active power- (QII+QIII) 

5.4.0 

4x40032 

4x40232 

FLOAT 

Sum Li Reactive power QI 

6.4.0 

4x40034 

4x40234 

FLOAT 

Sum Li Reactive power QII 

10 

7.4.0 

4x40036 

4x40236 

FLOAT 

Sum Li Reactive power QIII 

11 

8.4.0 

4x40038 

4x40238 

FLOAT 

Sum Li Reactive power QIV 

12 

1.6.1 

4x40040 

4x40240 

FLOAT 

Max Active Power - Import - Tariff 1 (kW) 

13 

1.6.1* 

4x40042 

4x40242 

FLOAT 

Max Active Power - Import - Tariff 1 (kW) - previous period 

14 

1.6.2 

4x40044 

4x40244 

FLOAT 

Max Active Power - Import - Tariff 2 (kW) 

15 

1.6.2* 

4x40046 

4x40246 

FLOAT 

Max Active Power - Import - Tariff 2 (kW) - previous period 

16 

1.6.3 

4x40048 

4x40248 

FLOAT 

Max Active Power - Import - Tariff 3 (kW) 

17 

1.6.3* 

4x40050 

4x40250 

FLOAT 

Max Active Power - Import - Tariff 3 (kW) - previous period 

18 

2.6.1 

4x40052 

4x40252 

FLOAT 

Max Active Power - Export - Tariff 1 (kW) 

19 

2.6.1* 

4x40054 

4x40254 

FLOAT 

Max Active Power - Export - Tariff 1 (kW) - previous period 

20 

2.6.2 

4x40056 

4x40256 

FLOAT 

Max Active Power - Export - Tariff 2 (kW) 

21 

2.6.2* 

4x40058 

4x40258 

FLOAT 

Max Active Power - Export - Tariff 2 (kW) - previous period 

22 

2.6.3 

4x40060 

4x40260 

FLOAT 

Max Active Power - Export - Tariff 3 (kW) 

23 

2.6.3* 

4x40062 

4x40262 

FLOAT 

Max Active Power - Export - Tariff 3 (kW) - previous period 

24 

1.8.0 

4x40064 

4x40264 

FLOAT 

Active Energy - Import - Total (kWh) 

25 

1.8.0* 

4x40066 

4x40266 

FLOAT 

Active Energy - Import - Total (kWh) - previous period 

26 

1.9.1 

4x40068 

4x40268 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 1 

27 

1.9.1* 

4x40070 

4x40270 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 1 - previous period 

28 

1.9.2 

4x40072 

4x40272 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 2 

29 

1.9.2* 

4x40074 

4x40274 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 2 - previous period 

30 

1.9.3 

4x40076 

4x40276 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 3 

31 

1.9.3* 

4x40078 

4x40278 

FLOAT 

Sum Li Active power+ (QI+QIV) - Tariff 3 - previous period 

32 

2.8.0 

4x40080 

4x40280 

FLOAT 

Active Energy - Export - Total (kWh) 

33 

2.8.0* 

4x40082 

4x40282 

FLOAT 

Active Energy - Export - Total (kWh) - previous period 

34 

2.9.1 

4x40084 

4x40284 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 1 

35 

2.9.1* 

4x40086 

4x40286 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 1 - previous period 

36 

2.9.2 

4x40088 

4x40288 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 2 

37 

2.9.2* 

4x40090 

4x40290 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 2 - previous period 

38 

2.9.3 

4x40092 

4x40292 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 3 

39 

2.9.3* 

4x40094 

4x40294 

FLOAT 

Sum Li Active power- (QII+QIII) - tariff 3 - previous period 

40 

5.8.0 

4x40096 

4x40296 

FLOAT 

Reactive Energy QI - Total (kvarh) 

41 

5.8.0* 

4x40098 

4x40298 

FLOAT 

Reactive Energy QI - Total (kvarh) - previous period 

42 

5.9.1 

4x40100 

4x40300 

FLOAT 

Sum Li Reactive power QI - Tariff 1  

43 

5.9.1* 

4x40102 

4x40302 

FLOAT 

Sum Li Reactive power QI - Tariff 1  - previous period 

44 

5.9.2 

4x40104 

4x40304 

FLOAT 

Sum Li Reactive power QI - Tariff 2 

45 

5.9.2* 

4x40106 

4x40306 

FLOAT 

Sum Li Reactive power QI - Tariff 2 - previous period 

46 

5.9.3 

4x40108 

4x40308 

FLOAT 

Sum Li Reactive power QI - Tariff 3 

47 

5.9.3* 

4x40110 

4x40310 

FLOAT 

Sum Li Reactive power QI - Tariff 3 - previous period 

48 

6.8.0 

4x40112 

4x40312 

FLOAT 

Reactive Energy QII - Total (kvarh) 

Summary of Contents for GW-DLMS-232-LG

Page 1: ...USER S MANUAL Gateway DLMS MODBUS for ISKRA with RS232 P N GW DLMS 232 LG Edition 2 0 MARCOM SRL Phone 390458204747 Email info marcomweb it Via Mezzacampagna 52 int 29 www marcomweb it...

Page 2: ...Revision Sheet Release No Date Revision Description Rev 0 10 05 14 User s Manual Template and Checklist Rev 1 10 06 16 Conversion to new format Rev 2 31 01 17 New HomeDLMS page Rev 3 20 05 18 New hard...

Page 3: ...0 compatibility 3 1 2 Features 4 1 2 1 Connections 4 1 2 2 Digital Input connection 4 1 2 3 Serial port connections 5 2 0 CONFIGURATION AND MODBUS MAP 6 2 1 Web Visualization 6 2 2 Communication with...

Page 4: ...ng MODBUS RTU or MODBUS TCP protocol The gateway is completely transparent to DLMS protocol so user must know only Modbus protocol This Gateway version reads data from up to two counters through the R...

Page 5: ...x Serial RS485 port to read energy meter s data by master Modbus RTU 1 x Ethernet port to read Energy meter s data by client Modbus TCP 1 screw connector to supply gateway 10 30 VDC min 2 W Front Sig...

Page 6: ...2 0 Configuration and Modbus map User s Manual GW DLMS 232 ISK Page 5 1 2 3 Serial port connections The schema of serial ports RS232 and RS485...

Page 7: ...ta read from the counter you need to connect to the network using the Ethernet RJ45 port available on the gateway By a web browser just type the default address 192 168 0 122 In case of connection fai...

Page 8: ...ually is standard Time between readouts can be set from 10 to 3600 seconds String debug is useful to understand the communication with meters With GATEWAY REBOOT button you can force the gateway to re...

Page 9: ...arity and ethernet such as the IP address just go to the Devices page and by clicking on the gear icon for the selected port a popup will open with the settings The two RS232 ports are COM0 and COM1 w...

Page 10: ...ue Refresh time of the values is approximately Time between readouts N where N is the number of energy meters connected to gateway and configured with a serial number different from zero in HomeDLMS M...

Page 11: ...rt Total kWh 25 1 8 0 4x40066 4x40266 FLOAT Active Energy Import Total kWh previous period 26 1 9 1 4x40068 4x40268 FLOAT Sum Li Active power QI QIV Tariff 1 27 1 9 1 4x40070 4x40270 FLOAT Sum Li Acti...

Page 12: ...active power QIV Tariff 1 previous period 68 8 9 2 4x40152 4x40352 FLOAT Sum Li Reactive power QIV Tariff 2 69 8 9 2 4x40154 4x40354 FLOAT Sum Li Reactive power QIV Tariff 2 previous period 70 8 9 3 4...

Page 13: ...0 4x41100 ULONG Reactive Energy QII Total kvarh previous period 8 7 8 0 4x41062 4x41102 ULONG Reactive Energy QIII Total kvarh 9 7 8 0 4x41064 4x41104 ULONG Reactive Energy QIII Total kvarh previous p...

Page 14: ...he type of error 5 serial port is not correctly opened 7 message from energy meter is too big for gateway s buffer this error does not compromise gateway s normal functionality but last part of obis l...

Page 15: ...7 0 Mechanical features User s Manual GW DLMS 232 ISK Page 14 4 0 MECHANICAL FEATURES The size of the gateway are the following...

Reviews: