6
Mareli Systems
3.3 Assembly of the duct components.
Duct components and pipes
For the assembly of the duct pipes the use of non-flammable materials, resistant to the flammable
products and condensation is obligatory. The assembly must be performed in such a manner so
it guarantees the airtight sealing and prevents condensation. If possible, avoid adding horizontal
sections. Direction shift is done by using knee joints with a max angle of 45˚.
For heating devices equipped with a smoke ventilator, i.e all of the “MARELI” stoves, the follow-
ing instructions must be observed:
•
Horizontal sections must have a minimum incline of 3° upwards;
•
The length of the horizontal sections must be as short as possible, but without exceeding 3
m;
•
More than four direction shifts are forbidden, including the cases where a T-shaped element
is used;
•
The duct components must be airtight and to be insulated if extending outside the premises
in which the fireplace is installed;
•
The duct components must allow a soot cleaning;
•
The duct components must have a constant section. A section change is allowed only in the
chimney joint;
Chimney
The chimney or the duct component must conform with the following requirements: to be air-
tight, waterproof and properly insulated, to be constructed with materials resistant to the normal
mechanical wear and to the heat coming from the combustion products and condensation.
•
To be kept away from flammable materials.
The recommended chimney draft at work - from 12-20 Pa.
Attention!!! In case of a fire hazard turn off the product from the display. This will stop the oxy-
gen flow to the product.
3.4 Types of connection to the chimney
Summary of Contents for PS 24
Page 13: ...13 Mareli Systems ...
Page 14: ...14 Mareli Systems ...
Page 15: ...15 Mareli Systems ...