Market Central, Inc.
R1000 NBS/NAC
Page 10 of 16
GET MANAGER
Display all SNMP manager IP addresses.
SAVE
Save settings for next startup. All settings are stored in NV memory and restored upon power on. Any change will
not become permanent until a SAVE and RESET operation sequence is performed.
RESET
Causes a network system reboot and reloads all parameters from stored settings.
HELP
Displays a list of commands.
>help
R1000 CONSOLE COMMANDS:
GET ALL (display all parameters)
GET VERSION (display software versions)
GET[SET] SYSTEM [A/B] (control all system ports)
GET RACK (display all ports)
GET[SET] PORT N [A/B] (control single port)
GET[SET] IPADDRESS [X.X.X.X]
GET[SET] SUBNETMASK [X.X.X.X]
GET[SET] GATEWAY [X.X.X.X]
GET[SET] READCOMMUNITYNAME [string]
GET[SET] WRITECOMMUNITYNAME [string]
GET[SET] WEBENABLE [ON/OFF]
GET[SET] WEBPASSWORD [string]
GET[SET] WEBTIMEOUT [N] (seconds)
GET[SET] WEBPORT [N]
GET[SET] TELNETENABLE: [on/off]
GET[SET] TELNETPASSWORD [string]
GET[SET] TELNETTIMEOUT N: (seconds)
GET[SET] TELNETPORT (N)
GET[SET] AUTHENTICATIONTRAP [ON/OFF]
GET[SET] MANAGER N [X.X.X.X] (0.0.0.0 to disable an entry)
GET MANAGER (display all SNMP managers)
SAVE save settings for next startup
RESET restart (use after SAVE)
Notes:
•
Commands can be entered in upper or lower case.
•
Models with less than 16 ports will display X in place of A or B when querying status.
•
All commands should be terminated with a carriage return (ASCII 13) or (hex 0x0D).
•
Set/get all and set/get port commands can be abbreviated using just first letters, i.e. “g a” for “get all” or “s
p 4 a” for “set port 4 a”.
•
* Remote (network) models use “get system” and “set system X” for “get/set all” commands. The
command “get all” returns all parameter settings (to be compatible with R5000 and R6000 command
structures).