 GENERAL INFORMATION 

 
Ratings:

   

Voltages: 120/230/277VAC, 50/60 Hz 
Loads: 

20A - 120/277VAC Ballast 

 

20A - 120VAC Incandescent 

 

1HP - 120/240VAC Motor 

 
Output:  150mA @ 24VDC (with relay 
connected) 
 
Low Voltage Input: 
Control ON: 

12-24VDC 

Hold ON:   

12-24VDC 

Hold OFF: 

12-24VDC 

Manual ON:  

12-24VDC (momentary switch required) 

 

Switching:  

SPST 

Operating temperature:  

 0°C to 55°C (32°F to 131°F ) 

 

NOTES:

 - 

Keep these instructions available for future reference.

 

 

- Indoor use only.

 

 
DESCRIPTION: 

The 6400 Power Pack is the core for any low-voltage lighting control 
system.  It supplies low-voltage power to occupancy sensors and other 
control devices and switches line voltage in response to signals from those 
devices.  It can be attached to existing junction boxes or mounted into 
fixture wiring trays. 
Low-voltage wiring should use at least 22 AWG wire.  High-voltage 
connections should use at least 14 AWG (12 AWG for 20A loads).  Always 
check local building codes. 
The power pack features zero-crossing circuitry to maximize relay life. 
 
 

 INSTALLATION 

 

CAUTION:

  INSTALLATION BY A LICENSED ELECTRICIAN IS RECOMMENDED.  

INSTALLATION AND USE OF THIS EQUIPMENT SHOULD BE IN ACCORDANCE WITH 
PROVISIONS OF THE U.S. NATIONAL ELECTRICAL CODE, APPLICABLE LOCAL 
CODES, AND PERTINENT INDUSTRY STANDARDS. 
 

CAUTION:

  USE THIS DEVICE WITH COPPER WIRE ONLY. 

 

CAUTION:

  IMPROPER WIRING CAN CAUSE DAMAGE TO THE POWER PACK, 

LIGHTING SYSTEM, OCCUPANCY SENSOR(S), AND OTHER CONTROL DEVICES. 
 

NOTE:

  

 POWER PACKS ARE DESIGNED TO ATTACH TO EXISTING OR NEW 

ELECTRICAL ENCLOSURES WITH 1/2 INCH KNOCKOUTS. 
 

NOTE:

  

 MOST APPLICATIONS REQUIRE UL LISTED, 18-22 AWG, 3-CONDUCTOR, 

CLASS 2 CABLE FOR LOW-VOLTAGE WIRING.  FOR PLENUM RETURN CEILINGS, 
USE UL LISTED PLENUM-APPROVED CABLES. 
 

NOTE:

  

 THIS POWER PACK IS A CLASS 2 OUTPUT POWER SUPPLY SUITABLE FOR 

PARALLEL INTERCONNECTION OF UP TO 6 UNITS MAXIMUM.  THIS POWER PACK 
IS UL LISTED FOR INTERCONNECTION OF POWER SOURCES IN ACCORDANCE 
WITH THE NATIONAL ELECTRICAL CODE. 

 

WARNING:  TO AVOID FIRE, SHOCK, OR DEATH, TURN OFF POWER 
AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF 
BEFORE WIRING! 

 
1)  Verify power has been turned off at the circuit breaker. 
2)  Refer to the mounting and wiring diagrams (Figure 1, and Figure 2 or 
Figure 3 as appropriate) and connect the wires as shown.  

Be sure all 

wire nuts are secure.

  Refer to the LOW-VOLTAGE INPUTS section for a 

description of the available switching options. 
 

NOTE:

  

 AFTER INITIAL WIRING IS COMPLETED, DOUBLE-CHECK WIRING 

DIAGRAMS TO VERIFY THE POWER PACK IS WIRED CORRECTLY. 

 

3)  Restore power at the circuit breaker. 
 
 

 
 
 

 WIRING DIAGRAMS 

                 

 

                                 

 

 

       
          

  

 

 
 
    
 
 

 

 
 
 
 

  

6400

  

Power Pack

       

  

 

                  INSTRUCTIONS

 

Figure 1: Typical Mounting & Wire Connections 

Figure 2:  Basic Wiring 