Rutland FM1803-2
Installation & Operation
Document No: SM-146 Issue G 01.11.20
Marlec Engineering Co Ltd
23
Awaiting Re-set V – Once fully charged the system remains stalled until the battery voltage
level reaches a lower limit for auto re-starting. Re-start can be manually invoked by 1 short
press of the Run/Stall button when the backlight is on, i.e. 2 short presses when the
backlight is off.
Other Modes/messages:
Low voltage - The bottom line of the screen will flash WARNING: LOW BATTERY. Charging
continues but the batteries may require additional charge for the given loads.
Over Temperature - The control unit has built in sensors to protect against over
temperature, the cooling fan will automatically switch on when the sensors detect a high
temperature within the controller components. If an over temperature occurs, the turbine
will stall & the source of the over temperature will display on the screen, when the over
temperature subsides, the control unit will resume normal operation & re-start the turbine.
The backlight will switch on & remain on for the duration of the warning.
Remote Shutdown
If the remote shutdown contacts are closed, the turbine will stall & ‘REMOTE SHUTDOWN’
will flash on the bottom line of the display.
RUN/STOP SWITCH – separately supplied and connected
This switch should be fitted to enable the user to shutdown the turbine enabling the
control unit to remain connected to the battery. If the control unit needs to be removed,
set the STOP position to hold the turbine in a stall position.