10
Close vent doors
No action required
Open vent doors
No
Yes
Reduce dry
damper opening
by an increment
Tower is in maximum
thermal performance
mode
Yes
Tower is in maximum plume abatement mode
Yes
No
Increase dry damper
opening by an increment
Is tower
pluming?
Are
vent doors
open?
Are dry
dampers
100%
open?
Is
CW
+
∆
CW
<
CW
MAX
?
Yes
No
No
Read cold water temp
CW
Is
CW
<
CW
MAX
?
Are dry
dampers
open?
Wait several minutes
Yes
No
No
Yes
Yes
No
Closing the vent doors will increase
CW
temp. If
CW
temp
is near
CW
MAX
then closing the doors may cause the
CW
temp to exceed
CW
MAX
. Opening the dry dampers will
increase the
CW
temp further.
∆
CW
may be determined by operating the tower with the vent
doors open and determining the
CW
temp,
CW
OPEN
. Then close
the vent doors and measure the
CW
temp,
CW
CLOSED
.
∆
CW
=
CW
CLOSED
–
CW
OPEN
. This value will vary depending on
the temp range (
HW
–
CW
) but is usually from 2° to 5°F.
Are
vent doors
open?
ClearSky Operation Logic Diagram