ELECTRICAL REQUIREMENTS
It is the responsibility of the spa owner to ensure that all electrical connections
are made by a qualified electrician in accordance with all national, state, and
local electrical codes in effect at the time of installation. Fuses are covered to
be free of defect at time of installation only.
240 Volt
All connections must be made in accordance with the wiring diagram found
on the inside of the control box cover. Connections must be made with
copper conductors only –
do NOT use aluminum wire.
All conductors, circuit
breakers, and fuses and the GFCi must be sized in accordance to the total
amperage load as specified below.
Improperly wired vessels can cause irreversible damage resulting in blown
fuse and melted terminal block, and to other electrical components. Also,
damage caused to components or equipment caused by high or low volt-
age, brown outs or electric surges is not covered under warranty.
• permanently connected (Hard wired).
• Rated 240V, 60Hz, 50A, three wires (#6 copper) plus ground (#8 copper
(8.42mm
2
)), [4 wires total].
• Circuit breaker or fuse size: 50A.
• A disconnecting means must be installed within sight from the equipment
and at least 5 feet (1.52m) from the inside walls of the spa.
• Connect only to a circuit protected by a Class A ground Fault Circuit inter
-
rupter (GFCi).
installation instructions