AS Martem Data Concentrator TELEM-GW6 User Manual
Akadeemia tee 21G Tel: +372 639 79 79 E-mail: martem@martem.eu
12618 Tallinn Fax: +379 639 79 80 www.martem.eu
Estonia
- 19 -
Hints
•
Repeated object addresses are shown on yellow background.
•
When leaving the Object Tab Card, all the objects are hidden. To see
the objects on returning to Object Tab Card, use Expand All from the
extended control menu that appears after a right click.
10.3.4 Formulas Tab Card
Figure 10.3.4 Formulas tab card
Columns:
•
Type, Sub Type , Invert, Object Adr ^, DB1 %Fs, DB2 %Fs, Crit.
Min %Fs, Crit. Max %Fs, Raw Min, Raw Max, Scale Min, Scale
Max, Forb.Ports - as in Objects Tab Card
•
LED no – The alarm (LED) number (1…16) on the LED Alarm panel
which corresponds with the result of this formula
•
DO addr. – Number of the digital output (1…16) in the TLM GW-IO
device controlled by the result of this formula
•
Execution count – The number of control operations executed, if no
feedback is received from control relay. Feedback must be determined
in the formula
•
Delay – Delay for execution in seconds
•
Forb. DO – The number of DO, which control is forbidden with the
result of this formula
•
LED Blinking – Determines if the LED that indicates the result of this
formula, remains blinking when corresponding signal disappears. The
LED remains blinking until the acknowledge button is pressed
•
Formula – Formula string