Configuration parameters of a port:
•
Protocol
– Communication protocol used by all the devices of this port.
Each protocol name is accompanied with a symbol ”^” or ”
ν
” which
indicates whether the port is used for an uplink or a downlink channel. For
example, “Modbus
ν
” means that this port is used for downlink with
Modbus protocol.
•
Baud rate
– Data communication rate
•
Parity
– Use of parity bit for all the devices on this channel
•
Stop Bit
– possible values are 1, 2
•
Data Bits
– possible values are 7, 8
•
Modem Settings
– GPRS modem connection check period
•
Communication Mode
– Makes it possible to choose between the
following handshaking options:
- No control
- TCP/IP Legacy
- TCP/IP Client
- TCP/IP Server
•
IP address
– communication IP address (used if Communication Mode is
set to TCP/IP)
a) 61850 v
IED IP Address
– an IP address of the
61850 device (server)
102 – (RFC 1006) IEC 61850 port of
ISO Transport on top of TCP
Interface
– eth0 or eth1 or eth2
Ethernet port
Provider Port
– TCP port of IEC 61850
provider, port 7001 is recommended
GPRS settings
– for GPRS modem ID
detection from TDC/IEC software
b)IEC ^ or IEC v
Other’s side IP Address
– an address
of the device which can connect with
GW6e using corresponding port (if set to
0.0.0.0 – all devices can connect)
Interface
– Any or eth0 or eth1 or eth2
Ethernet port
Port
– available network communication
port (in case of IEC 60870-5-104
protocol, port 2404 is recommended)