1. INTRODUCTION
This manual contains information and warnings which must be
followed to ensure safe operation of the IN2103.
1.1 Inspection
Examine the shipping carton for any sign of damage. Inspect the
unit and any accessories for damage. If there is any damage then
consult your distributor immediately.
You should have the following items:
1. IN2103
2. TL47A lead set
3. Instruction manual
4. Protective carry case with strap
5. Six LR6 alkaline batteries
6. Spare fuse (located in battery compartment)
1.2 Description
The IN2103 Digital Insulation and Continuity Tester is designed to
perform testing in accordance with international standards,
including BS7671. Insulation testing can be undertaken at
250/500/1000V DC. The tester is powered by six 1.5V alkaline
batteries type LR6.
To install or replace batteries refer to section
3.1
WARNING
READ "SAFETY INFORMATION" BEFORE USING THIS METER
2
))
) test
Auto-Discharge: when TEST button released
Buzzer: <30
Ω
Buzzer disable option: yes
k
Ω
test
Auto-Discharge: when TEST button released
Insulation test
Short circuit current: <1.5mA
Auto-Discharge: when TEST button released
Buzzer disable option: yes
Range
Resolution
Accuracy
999.9
Ω
0.1
Ω
±(3% rdgs +5d)
Range
Resolution
Accuracy
1999k
Ω
0.1
Ω
<999.9
Ω
1
Ω
>1000
Ω
±(3% rdgs +5d)
Voltage
Range
Resolution
Accuracy
250V
500V
1000V
4/40/400/1000M
Ω
4/40/400/4000M
Ω
4/40/400/5000M
Ω
1k
Ω/
10k
Ω/
100k
Ω/
1M
Ω
±(3%
rdgs +5d)