background image

3.3 Current measurement

1. Select the correct current range, using the rotary switch.
2. For inputs less than 200mA, connect the red test lead to the uA/mA
socket, and the black lead to the COM socket.
3. For inputs greater than 200mA, connect the red lead to the 10A socket,
& the black lead to the COM socket.
4. Remove power from the circuit, open the circuit path for the
measurement and connect the meter in series with it.
5 Apply power and take the reading shown on the display.

3.4 Resistance measurement

1. Select the required resistance range.
2. Remove power from the circuit under test.
3. Connect the red test lead to the "V

Ω

" socket and black lead to "COM"

socket.
4. Connect the test leads to the measurement points and take a reading.

3.5 Diode test

1. Select the "       " switch position.
2. Connect the red test lead to the "V

Ω

" socket and black lead to "COM"

socket.
3. Remove power from the circuit under test.
4. Touch the probes across the diode and take a reading, reverse the
probes and again take a reading. For a silicon diode, a value between 0.5
& 0.6 should be obtained in the forward direction, and "1." should be
displayed for the reverse direction. A value of "1." in both directions
indicates open circuit, a reading lower than 0.5 in either direction indicates
a shorted diode.

3.6 Battery test

1. Connect the red test lead to the "µA/mA" socket and black lead to
"COM".
2. Select either the 1.5V or the 9V "Batt" switch position.
3. Connect the test probes across the battery, a satisfactory reading for a
1.5V battery is >1.25V, and for a 9V battery is > 8.1V. Further information
regarding battery life may be obtained from the battery manufacturer.

1. INTRODUCTION

1.1 Description

The MM34 is a general purpose digital multimeter having average
responding AC voltage, DC voltage, DC current & resistance measurement
capability. Diode test & battery test functions are also present.

The 10A DC current range is separately fused, and has it's own test lead
connection socket. A different  connection socket is used for the remaining
DC current measurements.

Voltage and resistance readings are made with the test leads in the V

Ω

&

COM sockets.

A central rotary switch is used for the manual selection of the required
function, and range.

1.2  Unpacking & Inspection

Before unpacking the MM34, examine the shipping carton for any sign of
damage. Unpack and inspect the MM34 for any sign of damage. If there is
any damage then consult the supplier immediately.

1.3  Battery Installation

Refer to section 4.2 for battery installation instructions.

4

9

Summary of Contents for MM34

Page 1: ...ase rotation G Proving units G Socket Testers G Thermometers Probes G Test Leads G Voltage Indicators and G Specialist Metrohm testers 4 5kV G Specialist Drummond testers Martindale Electric Company Limited Metrohm House Penfold Trading Estate Watford WD24 4YY UK Tel 44 0 1923 441717 Fax 44 0 1923 446900 E mail sales martindale electric co uk Website www martindale electric co uk Martindale Electr...

Page 2: ...re available at www martindale electric co uk instruct html SYMBOLS Equipment complies with relevant EU Directives AC Alternating Current Ground Direct Current Equipment protected by Double Insulation Class II Caution refer to accompanying documents Caution risk of electric shock 4 4 Calibration The recommended calibration interval is 12 months Martindale Electric will carry out routine calibratio...

Page 3: ...placement WARNING To avoid electrical shock disconnect the test leads and any input signals before replacing the battery Replace only with the same type of battery This meter is powered by NEDA type 1604 or equivalent 9V battery When the meter displays the symbol the battery must be replaced to maintain proper operation To replace the battery remove the three screws from the back of the meter and ...

Page 4: ... both directions indicates open circuit a reading lower than 0 5 in either direction indicates a shorted diode 3 6 Battery test 1 Connect the red test lead to the µA mA socket and black lead to COM 2 Select either the 1 5V or the 9V Batt switch position 3 Connect the test probes across the battery a satisfactory reading for a 1 5V battery is 1 25V and for a 9V battery is 8 1V Further information r...

Page 5: ...irt grease etc Check the test leads for any evidence of cracked or frayed insulation If any abnormal conditions exist do not use the meter Warning When using probes keep your fingers behind the guards Warning Measuring voltages which exceed the limits of the meter may damage it and expose the operator to a shock hazard Always work within the meter voltage limits indicated on it s front panel Warni...

Page 6: ...ccuracy 3 rdg 1 digit Open circuit voltage 3V DC typical Overload protection 500V DC or AC rms BATTERY TEST Ranges 1 5V 9V Resolution 1mV 10mV Accuracy 3 5 rdg 2 digits Load current 150mA for 1 5V range typical 6mA for 9V range typical NOTE This instrument complies with class ll overvoltage CAT lll 600V of the IEC1010 1 EN61010 1 standard and pollution degree 2 in accordance with IEC 664 indoor us...

Reviews: