51
Figure 4-21 Setup-System Screen page 3
System setting can be set only when UPS is operating in certain mode. Please check available
setting item in Table 4-5 for the details. If it’s not set up in specific mode, the warning screen will
appear, as shown in Figure 4-22.
Figure 4-22 Warning screen
Setup-System setting list is shown in Table 4-8.
Table 4-8: Setup-System setting list
Setting Item Sub Item
Explanation
Output
Voltage
--
Set output voltage
220Vac (Default)
230Vac
240Vac
MUST be reviewed after UPS installation
BYPASS
SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
+10%
+15% (Default)
+20%