background image

TECHNICAL SPECIFICATIONS 

 

 

NOTE:

 Check the product label for your unit’s specifications.  

 

TROUBLESHOOTING 

 

Problem 

Possible Cause 

Solution 

AC power is 

available, but the 

outlets stopped 

providing power to 

connected 

equipment. 

Circuit breaker tripped due to an 

overload. 

Turn the UPS off and unplug at least one piece of equipment. Reset the circuit breaker by depressing the red button. 

Turn the UPS on.  

Low battery or battery voltage less 

than 10V.  

Allow the UPS to charge for at least 8 hours. The low battery may be due having recently experienced a power 

disturbance that drained the battery(ies) or the battery(ies) may need to be replaced with new ones.  

Control board failure. 

Control board needs to be replaced. Contact or your local authorized retailer for fastest support. You can also contact 

us at 

support@marusonusa.com.

 

AC power voltage is beyond accepted 

range.  

 

If the UPS detects the incoming AC power to be below or above the accepted voltage range, the UPS will not power on to 

protect connected equipment. Please wait a few minutes before turning on the UPS.

 

The UPS is always 

in Battery Mode. 

Power cord is loose.  

Check the power input connection at the mains and input connection on the UPS to power supply cord.  

Circuit breaker tripped.  

Turn the UPS off. Reset the circuit breaker by depressing the red button. Turn the UPS on.  

Control board failure. 

Control board needs to be replaced. Contact or your local authorized retailer for fastest support. You can also contact 

us at 

support@marusonusa.com.

 

The battery does 

not perform to the 

expected runtime. 

Battery is not fully charged or has 

not recharge fully since last time 

battery backup mode. 

Allow the UPS to recharge fully by leaving the UPS plugged in.  

The UPS is overloaded. 

Remove at least one non-critical equipment. Keep removing equipment until the UPS is no longer overloaded.  

End of battery service life.  

Replace battery or contact 

support@marusonusa.com.

 

Battery defect.  

If the battery is less than one year old, it the shorter runtime may be due to operating in high temperatures or improper 

operation of the battery. Replace the battery with the same type of battery.  

 

If replacing the battery does not resolve the issue, contact your local authorized retailer. You may also contact us at 

support@marusonusa.com.

 

UPS beeps 

continuously.  

UPS is overloaded. 

Turn the UPS off and unplug at least one piece of equipment before turning the UPS back on. 

 

LIMITED WARRANTY 

The 650VA / 850VA / 1200VA / 1650VA / 2200VA Power Pro LCD (individually and collectively, the “Product”) includes limited warranties Maruson Technology Corporation 

(referred to herein as “Maruson”) offers for customers who register their product within fifteen (15) days of the invoice date. These limited warranties are only for the original end-

user (“Original Purchaser”). Please retain a copy of your receipt as proof of purchase. All Warranty claims must be made within ten (10) days of occurrence. If you need to file a 

claim, contact your local authorized dealer first or fill out the RMA form online from the Maruson website. Terms and conditions apply. Visit our website for details. To register your 

product, go to 

www.MarusonUSA.com

 > 

Support

 > 

Registration

 (left column).  

 

Maruson warrants the Original Purchaser of this Product that the product is free from defects in materials and workmanship under normal use and service for which the product 

was designed for a period of three (3) years for Limited Product and two (2) years for Limited Battery Warranty. The limited warranties start date is based on the date of purchase. 

If, in the opinion of Maruson, the UPS or battery is defective and defective within the scope of this warranty, Maruson’s sole obligation will be to repair or replace the defective 

UPS or battery. No salesperson, employee, or agent of Maruson is authorized to add to or vary the terms of the warranties. By using the Product, you agree to the terms of the 

Limited Warranty. The duration of warranty coverage does not pause, restart, or extend if the Product is with Maruson or any of its dealers for evaluation, servicing, repairs, or if a 

replacement part or unit is provided.  

 

If any payment is required as part of a service, Maruson’s obligations under this warranty are expressly conditioned upon receipt by customer of all payments due to it (including 

interest charges, if any). During such time as Maruson has not received payment of any amount due to it for the Product, in accordance to the contract terms under which the 

Product is sold, Maruson shall have no obligation under this warranty.  

 

WHAT IS NOT COVERED 

Maruson shall not be liable for costs, damages, or repairs incurred as a result of, due to, or from: 

  Warranty for purchase of unit from unauthorized dealers, second-hand units, or units that were transferred.  

  Improper usage, operation, handling, tampering, misuse, abuse, lack of maintenance, and/or use of the UPS or connected equipment not in accordance with the User 

Manual.  

  Damage from fire, flood, wind, rain, rising water, theft, vandalism, lightning, or other acts of God, leakage or breakage of plumbing, harsh chemical action, intentional 

misconduct on the part of the consumer, accident, dropping the device, abuse or other abnormal conditions, or unauthorized modifications.  

  Normal wear and tear, including normal wearing parts such as the power cord (or where external damage or abuse was diagnosed). 

  Damage from lightning or power transients. Damage from causes other than AC power line transients, spikes, or surges on properly installed, grounded and code-compliant 

120Vac power lines; transient surges or spikes on standard telephone land lines, PBX telephone equipment, or base 10T ethernet lines, when properly installed   

  Economic loss or special, indirect, or consequential including without limitations; loss or damage to data, records, or software or the restoration of data or records, or the 

restoration of software, whether or not on account of product failure.  

  Damage as a result of use not in accordance with the rating plate.  

  Units with the serial number altered or removed.  

  Reduction of battery discharge time due to battery age or use.  

  Packaging and shipping costs to ship from the customer to Maruson for warranty service.  

 

DISCLAIMER OF WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY AND WARRANTY OF FITNESS FOR PARTICULAR PURPOSE: EXCEPT AS 

SPECIFICALLY SET FORTH HEREIN, NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, IS MADE AS TO THE UPS. EXCEPT AS EXPRESSLY SET 

FORTH HEREIN, MARUSON AND/OR ITS AFFILIATES EXPRESSLY DISCLAIMS, WITHOUT LIMITATION, ANY STATUTORY WARRANTIES, AND ALL IMPLIED 

WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL MARUSON, ITS 

AFFILIATES, ASSOCIATES, DEALERS, AGENTS OR SUPPLIERS OR THEIR RESPECTIVE OFFICERS, DIRECTORS, EMPLOYEES, AND ASSIGNS BE LIABLE FOR 

INCIDENTAL, SPECIAL, DIRECT, INDIRECT, EXEMPLARY, PUNITIVE, SPECIAL, CONSEQUENTIAL, OR MULTIPLE DAMAGES SUCH AS, BUT NOT LIMITED TO 

BUSINESS INTERRUPTION, LOST BUSINESS OR PROFITS, PERSONAL INJURY, LOSS OF ABILITY TO USE THIRD-PARTY PRODUCTS OR SERVICES, FAILURE TO 

MEET ANY DUTY INCLUDING OF GOOD FAITH OR REASONABLE CARE, NEGLIGENCE, OR LOSS OF DATA ARISING OUT OF THE SALE, USE, OR INABILITY TO USE 

OF ANY MARUSON UPS, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. IN NO EVENT SHALL THE TOTAL AGGREGATE LIABILITY OF MARUSON, ITS 

AFFILIATES, ASSOCIATES, DEALERS, AGENTS OR SUPPLIERS TO YOU FOR ALL DAMAGES EXCEED THE PRICE YOU PAID FOR THE PRODUCT. THIS LIMITATION 

IS CUMULATIVE AND WILL NOT BE INCREASED BY THE EXISTENCE OF MORE THAN ONE INCIDENT OR CLAIM. THE FOREGOING LIMITATIONS WILL APPLY EVEN 

IF ANY WARRANTY OR REMEDY PROVIDED FAILURES OF ITS ESSENTIAL PURPOSE. NOTHING IN THIS SECTION SHALL LIMIT THE LIABILITY OF MARUSON IN 

RELATION TO DEATH OR BODILY INJURIES. THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN CONNECTION WITH ANY NUCLEAR, MEDICAL, 

LIFE-SUPPORT, AND RELATED APPLICATIONS.  

 

This warranty gives you specific legal rights, and you may also have other rights, which may vary from state to state. Some states or provinces do not allow the exclusion or 

limitation of incidental or consequential damage, so the limitations stated may not apply to you. The English version of this warranty and policy will always prevail if there are 

inconsistencies with a translated version. 

 

SUPPORT 

If the unit requires service or you are having difficulty using the unit, follow these steps:   

1.  Review the Troubleshooting section of the manual to see if that resolves the issue.  

2.  Contact your local authorized distributor for support. If you are not able to get ahold of your local authorized distributor, contact Maruson Technical Support at +1-800-627-8766 

o

support@marusonusa.com

. We’re available Monday through Friday, 9 AM to 5 PM (Pacific Time). We will need your model number, serial number, and description of issue 

and connected equipment for support.  

a.  If we are unable to resolve the issue over phone or email, the technician will issue a Return Authorization Number (RMA #) to ship the unit back for repair.  

b.  If the unit is under warranty, the repairs are free.  

3.  Pack the unit in the original packaging to avoid damage during transit. Damage sustained during transit and lost packages on the way to or from Maruson are not covered 

under warranty. The customer is responsible for all shipping costs (including duties and taxes if outside US) to ship to and from Maruson.  

4.  The RMA number must be marked on the outer packaging and return the unit by insured, pre-paid carrier to the address provided by the technician. Packages without an RMA 

number on the outside package and collect shipments will be refused.  

 

BATTERY REPLACEMENT 

Carefully read the cautions and warnings in this manual before attempting to replace the batteries; not doing so can cause serious injury, shock, or fire. 

Failure to connect to 

the correct terminals may cause damage to the UPS, battery(ies), or other damages. 

It is normal for small sparks to be seen when the battery cable is connected the 

battery terminal. Recycle spent batteries. Always use new batteries for replacement, do not use recycled batteries.  

 

1.  Turn off and unplug all connected equipment from the UPS. Turn off the UPS and unplug the unit 

from the AC power source. 

2.  Remove the two screws under the UPS’ front panel with a Phillips screwdriver.  

3.  Carefully remove the front panel from the UPS by lifting the bottom of the front panel outward from 

the UPS and upward.  

4.  Remove the plastic mount in front of the battery(ies) by sliding it up.  

5. 

650VA / 850VA Models:

 Remove the spent battery from the UPS. Disconnect the 

black 

(

negative

-

) wire from the battery terminal, then disconnect the 

red

 (

positive

+

) wire. When replacing with a 

new battery, connect the 

red

 (

positive

+

) wire to the 

positive

 (

+

) terminal first, then connect the 

black

 (

negative

-

) wire to the 

negative

 (

-

) battery terminal.  

1200VA / 1650VA / 2200VA Models:

 Remove the spent batteries from the UPS. Disconnect the 

black

 (

negative

-

) wire from the first battery, then remove the jumper wire from the 

negative

 (

-

terminal on the second battery. Next, remove the jumper wire from the 

positive

 (

+

) terminal on the 

first battery, before removing the 

red

 (

positive

+

) wire from the second battery. Remove the spent 

batteries from the UPS and place the new batteries into the battery compartment for wiring.  

 

When replacing with new batteries, connect the wires in reverse. Connect the 

red 

(

positive

+

) wire 

to the 

positive

 (

+

) terminal on the second battery, then connect one end of the jumper wire to the 

positive

 (

+

) terminal on the first battery. Next, connect the other end of the jumper wire to the 

negative

 (

-

) terminal on the second battery. Finish up by connecting the 

black 

(

negative

-

) wire to 

the negative battery terminal of the first battery.  

6.  Replace the battery compartment cover. Plug the UPS to a wall outlet to recharge the UPS battery for 

at least 6 hours before turning the UPS on for use.   

 

  

 

 

 

 

 

 

© 2021 Maruson Technology Corporation. Maruson, Maruson Technology, and the Maruson logo are owned by Maruson Technology Corporation or their affiliated companies. All 

other trademarks mentioned are the property of their respective owners. The information contained herein is subject to change without notice. While every precaution has been 

taken to ensure accuracy and completeness herein, Maruson assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any 

errors or omissions.  

 

Maruson Technology | PO Box 1986, Walnut, CA 91788, USA | www.MarusonUSA.com                                                 

               

 

        

 

 

701-0071624 UPS-Mar-Pro-NLCD-01 

Model

 

PRO-650LCD 

PRO-850LCD 

PRO-1200LCD 

PRO-1650LCD 

PRO-2200LCD 

Capacity 

650VA / 390W 

850VA / 510W 

1200VA / 720W 

1650VA / 990W 

2200VA / 1320W 

Nominal Voltage 

110 /115 / 120Vac or 220 / 230 / 240Vac 

Input Voltage Range  

110 / 115 / 120Vac models: 80 – 145 Vac; or 

220 / 230 / 240Vac models: 154 – 280 Vac 

Frequency Range 

47 – 63 Hz (auto sensing) 

Output Voltage 

110 /115 / 120Vac or 220 / 230 / 240Vac 

Regulation Steps  

2-Steps Up and 1-Step Down Automatic Voltage Regulation 

On-Battery Output Wave Form 

Simulated Sine Wave 

On-Battery Output Voltage 

110 /115 / 120Vac or 220 / 230 / /- 10% 

On Battery Output Frequency 

50 / 60 Hz +/- 1% 

Battery Type 

Sealed Maintenance-Free Lead Acid Battery 

Battery Size 

12V / 7.2Ah x 1  

12V / 9Ah x 1  

12V / 7.2Ah x 2  

12V / 9Ah x 2 

12V / 9Ah x 2  

Battery Charging Voltage 

13.7Vdc +/- 2% 

27.4Vdc +/- 2% 

Battery Recharge Time 

Typically, < 5 hours to 90% Capacity  

Transfer Time 

2 – 6 ms (typical) 

Full Protection 

Discharge, Overcharge, and Overload Protection 

EMI Filtering 

Yes  

Surge Protection 

320 Joules 

480 Joules 

USB Communication Port 

Yes 

Phone / Fax / Network Surge 

Protection 

RJ-11 / 45 (1-in, 1-out)  

(650VA & 850VA models with Thailand type sockets will not have this feature.) 

Power Management Software 

Yes, Windows® 10 / 8 / 7 / 2008 / 2003 / 2000, Server® 2012 R2 / 2008 R2, Linux®, Unix, Mac® 

Auto-Charger 

Yes 

Auto-Restart 

Yes 

Operating Temperature 

0°C up to 40°C / 32 up to 104 °F 

Operating Relative Humidity  

0 to 90% Non-Condensing 

Noise Level 

Less Than 40 dB 

Dimensions (DWH) 

315.5 x 100 x 141 mm / 12.4 x 3.9 x 5.6 in 

343 x 135 x 208 mm / 13.5 x 5.3 8.23 in 

Product Weight 

4,7 kg / 10.4 lb 

5,7 kg / 12.6 lb 

8,1 kg / 17.9 lb 

9,7 kg / 21.4 lb 

11,4 kg / 25.1 lb 

Align the arrows on the battery 

compartment cover with the 

UPS to remove the cover. 

 

 

 

 

 

 

1200-2200VA Wires Removal:  

1.  Remove 

black (-)

 wire first.  

2.  Remove jumper wire on the 

negative terminal of the 

second battery.  

3.  Remove the jumper wire 

from the positive terminal on 

the first battery.  

4.  Remove 

red (+)

 

wire. 

5.  Reverse the steps when 

installing new batteries.    

Reviews: