4. Panel Description 

 

 

 

 

 

 

 

 

 

 

 

The Display Panel

 

Switch 

Function 

ON-Button 

Turn on UPS system: 
By pressing the ON-Button “I” the UPS system is turned on. 
Deactivate acoustic alarm: 
By pressing this Button an acoustic alarm can be deactivated. 

OFF-Button 

When mains  power  is  normal,  the UPS system switches to  No 
output  or  Bypass  mode  by  pressing  OFF-Button  “ “,  and  the 
inverter  is  off.  At  this  moment,  if  Bypass  is  enabled,  then  the 
output  sockets  are  supplied  with  voltage  via  the  bypass  if  the 
mains power is available. 

Select-Button 

If  the  UPS  system  is  No  output  or  Bypass  mode,  the  output 
voltage  and  frequency  and  Bypass  disable/enable  could  be 
selected by pressing Select-Button, and confirmed by pressing 
Enter-Button. 

Enter-Button 

If  the  UPS  system  is  No  output  or  Bypass  mode,  the  output 
voltage  and  frequency  and  Bypass  disable/enable  could  be 
selected by pressing Select-Button, and confirmed by pressing 
Enter-Button. 

 

-31- 

9. Maintenance 

9.1 Operation 

The  UPS  system  contains  no  user-serviceable  parts.  If  the  battery 

service  life  (3~5  years  at  25°C  ambient  temperature)  has  been 

exceeded, the batteries must be replaced. In this case please contact 

your dealer. 

9.2 Storage 

If the batteries are stored in temperate climatic zones, they should be 

charged  every  three  months  for  1~2  hours.  You  should  shorten  the 

charging  intervals  to  two  months  at  locations  subject  to  high 

temperatures. 

9.3 Battery Replace 

If the battery  service  life  has  been exceeded, the  batteries must  be 

replaced. 

Battery replacement should be performed only by qualified personnel. 

It recommends to shut off the UPS completely before the replacement. 

If there is a battery breaker then turn it off first. Disconnect the battery 

cable carefully and make sure no any exposed wires can be to uched. 

Reconnect  the  new  batteries  to  the  UPS  by  following  section  5.8. 

Then turn on the battery breaker and start the UPS. 

If  it  needs  to  replace  the  batteries  while  the  UPS  is  running,  make 

sure the UPS would not shut down during the replacement. If there is 

a  battery  breaker  then  turn  it  off  first.  Disconnect  the  battery  cable 

carefully  and  make  sure  no  any  exposed  wires  can  be  touched. 

Reconnect  the  new  batteries  to  the  UPS  by  following  section  5.8. 

Then turn on the battery breaker and press the ON switch to make the 

UPS  do  the  battery  test,  check  whether  the  battery  information  is 

normal. 

Summary of Contents for TAC-HV1K

Page 1: ...fo MarusonUSA com Copyright 2012 All Rights Reserved Maruson is a registered trademark ofMaruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respective own...

Page 2: ...scription 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function...

Page 3: ...9 1 Operation 31 9 2 Storage 31 9 3 Battery Replace 31 10 Technical Data 32 10 1 Electrical specifications 32 10 2 Operating Environment 32 10 3 Typical backup time Typical values at 25 C in minutes 3...

Page 4: ...t sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip...

Page 5: ...remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal b...

Page 6: ...carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are...

Page 7: ...the room where it is ventilated and dry 35 12 Software Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control you...

Page 8: ...tion I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 In...

Page 9: ...urself with them and understand their meaning 33 10 3 Typical backup time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimen...

Page 10: ...uninterruptible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers The double converter principle eliminates all...

Page 11: ...ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hour...

Page 12: ...Indicates the input Line voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line v...

Page 13: ...nside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation L...

Page 14: ...tify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature 11 Indicates the UPS is working in bypass mode the load is d...

Page 15: ...eaker or protective components to the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB...

Page 16: ...the output sockets to complete connection Use one cord for every 10A load Model No Output Socket pcs 1K L 3 IEC type 2K L 6 IEC type 3K L 4 IEC type The wiring configuration is shown as the following...

Page 17: ...e the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it...

Page 18: ...ding value after the right values are selected on the LCD panel and the UPS is turn on by pressing the ON Button The UPS would turn to bypass mode in several seconds after Bypass Enable is selected an...

Page 19: ...turn it off first 5 Remove the small cover of terminal block prepare the battery cable which should be able to carry the current of 30A for 1KVA 22A for 2KVA 33A for 3KVA the cross section area shoul...

Page 20: ...loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc The No output m...

Page 21: ...lity power the battery the UPS output and the load could be displayed The word of LINE indicates the inverter of the UPS is working The operating mode code of the UPS is 2 21 battery mode code of the...

Page 22: ...same as battery mode but High and Low would not be shown unless the input line voltage is higher or lower than the SPEC range during the time of battery test The The Battery mode 19 If output overload...

Reviews: