If the UPS system does not operate correctly, please attempt to solve the 

problem using the table below. 

Problem 

Possible cause 

Remedy 

No indication, no 
warning tone even 
though system is 
connected to mains 
power supply 

No input voltage 

Check building wiring 
socket outlet and input 
cable. 

Display Mode 
code ”1” in LCD, 
even though the 
power supply is 
available 

Inverter 

not 

switched on 

Press On-Switch “I”. 

Display Mode 
code ”3” in LCD, and 
audible alarm 
sounding every 1 
beep in every 4 
seconds 

Mains power 
supply has failed, 
or Input power 
and/or frequency 
are out of tolerance 

Switching to battery mode 
automatically.   
Check input power source 
and inform dealer if 
necessary. 

Emergency supply 
period shorter than 
nominal value 

Batteries  not  fully 
charged  /  batteries 
defect 

Charge  the  batteries  for  at 
least   
5 - 8 hours and then check 
capacity. If the problem still 
persists, consult your 
dealer. 

Fan fail 

Fan abnormal   

Check if the fan is running 

Battery over voltage 

Battery is over 
charged 

Switching to battery mode 
automatically, and after the 
battery voltage is normal 
and the mains is normal, the 
UPS would Switching to line 
mode automatically again. 

Battery low 

Battery voltage is 
low 

When audible alarm 
sounding every second, 
battery is almost empty. 

Charge fail 

The charge is 
broken 

Notify dealer. 

DC-DC temperature 
high 

Inside temperature 
of the UPS is too 
high 

Check the ventilation of the 
UPS, check the ambient 
temperature. 

 

-11- 

 

 

Indicates the UPS is working in bypass mode, the 
load  is  directly  supplied  by  the  input  power 
through bypass 

 

Indicates the UPS is working in no output mode 

   

 

Indicates the UPS is working in line mode 

 

 

Indicates the UPS is working in battery mode 

 

Indicates the UPS is working in fault mode 

 

Indicates  some  warnings  occur  which  need  be 
attention 

 

Indicates  the  UPS  is  abnormal  in  which  some 
faults or warnings occur 

Output  voltage  and  frequency  and  Bypass  disable/enable 
selection Information 

 

The  four  value  of  the  output  voltage  could  be 
selected when the UPS is in No output or Bypass 
mode, and only one of them could be active in the 
same time. Derating 10% when the output voltage 
is adjusted to 208VAC 

 

The  two  frequency  value  of  the  output  voltage 
could be selected when the UPS is in No output or 
Bypass  mode,  and  only  one  of  them  could  be 
active in the same time 

 

Bypass disable or enable could be selected when 
the UPS is in No output or Bypass mode, and only 
one of them could be active in the same time 

 

(1) Here wo uld become 

  instead when the user 

does operating mode of UPS setting. 

      “UPS” means the setting of normal inverter mode (Line mode). 

      “ECO” means the setting of economy mode. 

      “CVF” means the setting of converter mode. 

The  detail  illustration  of  the  three  modes  and  the  operation  of  the 

setting would be presented in the following section. 

 

Summary of Contents for TAC-HV1K

Page 1: ...fo MarusonUSA com Copyright 2012 All Rights Reserved Maruson is a registered trademark ofMaruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respective own...

Page 2: ...scription 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function...

Page 3: ...9 1 Operation 31 9 2 Storage 31 9 3 Battery Replace 31 10 Technical Data 32 10 1 Electrical specifications 32 10 2 Operating Environment 32 10 3 Typical backup time Typical values at 25 C in minutes 3...

Page 4: ...t sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip...

Page 5: ...remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal b...

Page 6: ...carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are...

Page 7: ...the room where it is ventilated and dry 35 12 Software Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control you...

Page 8: ...tion I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 In...

Page 9: ...urself with them and understand their meaning 33 10 3 Typical backup time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimen...

Page 10: ...uninterruptible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers The double converter principle eliminates all...

Page 11: ...ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hour...

Page 12: ...Indicates the input Line voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line v...

Page 13: ...nside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation L...

Page 14: ...tify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature 11 Indicates the UPS is working in bypass mode the load is d...

Page 15: ...eaker or protective components to the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB...

Page 16: ...the output sockets to complete connection Use one cord for every 10A load Model No Output Socket pcs 1K L 3 IEC type 2K L 6 IEC type 3K L 4 IEC type The wiring configuration is shown as the following...

Page 17: ...e the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it...

Page 18: ...ding value after the right values are selected on the LCD panel and the UPS is turn on by pressing the ON Button The UPS would turn to bypass mode in several seconds after Bypass Enable is selected an...

Page 19: ...turn it off first 5 Remove the small cover of terminal block prepare the battery cable which should be able to carry the current of 30A for 1KVA 22A for 2KVA 33A for 3KVA the cross section area shoul...

Page 20: ...loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc The No output m...

Page 21: ...lity power the battery the UPS output and the load could be displayed The word of LINE indicates the inverter of the UPS is working The operating mode code of the UPS is 2 21 battery mode code of the...

Page 22: ...same as battery mode but High and Low would not be shown unless the input line voltage is higher or lower than the SPEC range during the time of battery test The The Battery mode 19 If output overload...

Reviews: