-14- 

(3) EPO Connection: 

User  can  select the  polarity  of EPO, EPO  is Normally  Close for 
the UPS 

 

Normally the EPO connector is open on the rear panel. Once the 
connector is  closed with a  wire,  the UPS wo uld  stop the  output 
until the EPO status is disabled. 

 

Disable the EPO status

                 

Enable the EPO status 

 

Normally  the  EPO  connector  is  closed  with  a  wire  on  the  rear 
panel.  Once  the  connector  is  open,  the  UPS  would  stop  the 
output until the EPO status is disabled. 

 

Enable the EPO status                    Disable the EPO status

     

 

5.3 Battery charge:   

Fully  charge  the  batteries  of  the  UPS  system  by  leaving  the  UPS 

system connected to the mains for 1-2 hours.  You may use the UPS 

system directly witho ut charging it but the stored energy time may be 

shorter than the nominal value specified. 

5.4 Turn on the UPS:   

(1) With utility power connecting:   

Press “I” button continuously for more than 1 second to turn on the 

 

-25- 

  Here is a example for changing the output voltage from 220Vac to 

230Vac through the LCD panel. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Setp  1: 

One  flickering  black  dot  would  appear  before 
“208Vac” after pressing the “Select” button. 

Setp  2: 

The  flickering  dot  would  move  to  “230Vac”  after 

pressing the “Select” button two times again. 

Summary of Contents for TAC-HV1K

Page 1: ...fo MarusonUSA com Copyright 2012 All Rights Reserved Maruson is a registered trademark ofMaruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respective own...

Page 2: ...scription 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function...

Page 3: ...9 1 Operation 31 9 2 Storage 31 9 3 Battery Replace 31 10 Technical Data 32 10 1 Electrical specifications 32 10 2 Operating Environment 32 10 3 Typical backup time Typical values at 25 C in minutes 3...

Page 4: ...t sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip...

Page 5: ...remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal b...

Page 6: ...carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are...

Page 7: ...the room where it is ventilated and dry 35 12 Software Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control you...

Page 8: ...tion I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 In...

Page 9: ...urself with them and understand their meaning 33 10 3 Typical backup time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimen...

Page 10: ...uninterruptible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers The double converter principle eliminates all...

Page 11: ...ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hour...

Page 12: ...Indicates the input Line voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line v...

Page 13: ...nside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation L...

Page 14: ...tify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature 11 Indicates the UPS is working in bypass mode the load is d...

Page 15: ...eaker or protective components to the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB...

Page 16: ...the output sockets to complete connection Use one cord for every 10A load Model No Output Socket pcs 1K L 3 IEC type 2K L 6 IEC type 3K L 4 IEC type The wiring configuration is shown as the following...

Page 17: ...e the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it...

Page 18: ...ding value after the right values are selected on the LCD panel and the UPS is turn on by pressing the ON Button The UPS would turn to bypass mode in several seconds after Bypass Enable is selected an...

Page 19: ...turn it off first 5 Remove the small cover of terminal block prepare the battery cable which should be able to carry the current of 30A for 1KVA 22A for 2KVA 33A for 3KVA the cross section area shoul...

Page 20: ...loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc The No output m...

Page 21: ...lity power the battery the UPS output and the load could be displayed The word of LINE indicates the inverter of the UPS is working The operating mode code of the UPS is 2 21 battery mode code of the...

Page 22: ...same as battery mode but High and Low would not be shown unless the input line voltage is higher or lower than the SPEC range during the time of battery test The The Battery mode 19 If output overload...

Reviews: