7. Setting by LCD Module

 

The output voltage and frequency, and bypass state, and ECO mode, and 

Converter  mode  could  be  set  directly  thro ugh  LCD  module.  The  output 

voltage could be set to 208V, 220V, 230V and 240V. The output frequency 

could be set to 50Hz and 60Hz. The operating mode of UPS could be set 

between  the  Line  mode,  ECO  mode  and  Converter  mode.  The  bypass 

state could be set to enable and disable. But all the settings could only be 

done when the UPS is in bypass or no output mode. 

In  bypass  or  no  output  mode,  pressing  the  “Select”  button  on  the  LCD 

panel  for  more  than  one  second,  a  flickering  black  dot  would  be  shown 

before  “208V”  on  the  screen.  And  if  pressing  the  “Select”  button 

continuously again, the flickering black dot would move to “220V”, next to 

“230V”,  “240V”,  “50Hz”,  “60Hz”,  “Bypass  Disable”,  “Bypass  Enable”,   

“UPS”,  “ECO”,  “CVF”  in  turn.  (Here  “UPS”  means  the  normal  inverter 

mode, and “UPS”, “ECO”, and “CVF” would be presented circularly at the 

position of output voltage) And if pressing the “Enter” button for more than 

one  second  at  this time, the  flickering  black dot would  turn  to  flickerless 

and the output voltage or frequency or bypass state or mode state setting 

would  be  modified  to  the  selected  value.  And  if  no  any  pressing  on  the 

“Select” or “Enter” button  lasting for more than 30 seconds, the flickering 

black dot would disappear. 

The only one  voltage  value  could be  selected in  “208V”,  “220V”,  “230V”, 

“240V”  at  any  time.  The  only  one  frequency  value  could  be  selected  in 

“50Hz”, “60Hz” at  any time.  And the  output  voltage  and  frequency  would 

be changed to the corresponding value after the right values are selected 

on  the LCD  panel  and the  UPS is  turn  on  by  pressing  the  “ON” Button. 

The  UPS  would  turn  to  bypass  mode  in  several  seconds  after  “Bypass 

Enable” is selected, and turn to no output mode in several seconds after 

“Bypass Disable” is selected. The mode change would be active only after 

the UPS is turned on. 

 

-15- 

UPS, the UPS will get into the inverter mode, the LCD screen will 

indicate the state of the UPS.   

(2) Without utility pow er connecting:   

If UPS  is cold start without  utility power  connecting, user  need to 

push  “I”  button  twice, first  pushing  “I”  button  is  for  UPS to  get 

power, and second pushing “I” button continuo usly for more than 1 

second  is  for  UPS  to turns  on,  the  UPS  will  get  into  the  inverter 

mode.  In  fact,  the  two  pushing  “I”  button  is  to  make  further  sure 

user operation for turning on UPS, the LCD screen will indicate the 

state of the UPS.   

Note: The default setting for bypass mode is no output after UPS 

is connecting utility power and breaker is turned on. This can be 

configured by monitoring the LCD panel or firmware. 

5.5 Test function:   

Test the function of the UPS system by pressing the On-Switch “I” for 
more  than  1  second,  the  UPS  would  detect  whether  the  battery  is 
connected or the battery is  low. And the UPS could also do the test 
automatically and periodically, the period time could be set by user. 

5.6 Turn off the UPS: 

(1) In Inverter Mode:   

Press “ “ button continuously for  more  than  1  seco nd  to  turn off 

the UPS, the UPS will get into  no output or bypass mode.  At this 

time,  the UPS might  has o utput if  bypass is enabled. Disconnect 

the utility power to turn off the output.   

(2) In Battery Mode:   

Press  “ “ button continuously for  more  than  1 second to  turn off 

the UPS, the UPS will be turned off completely. 

Summary of Contents for TAC-HV1K

Page 1: ...fo MarusonUSA com Copyright 2012 All Rights Reserved Maruson is a registered trademark ofMaruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respective own...

Page 2: ...scription 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function...

Page 3: ...9 1 Operation 31 9 2 Storage 31 9 3 Battery Replace 31 10 Technical Data 32 10 1 Electrical specifications 32 10 2 Operating Environment 32 10 3 Typical backup time Typical values at 25 C in minutes 3...

Page 4: ...t sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip...

Page 5: ...remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal b...

Page 6: ...carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are...

Page 7: ...the room where it is ventilated and dry 35 12 Software Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control you...

Page 8: ...tion I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 In...

Page 9: ...urself with them and understand their meaning 33 10 3 Typical backup time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimen...

Page 10: ...uninterruptible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers The double converter principle eliminates all...

Page 11: ...ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hour...

Page 12: ...Indicates the input Line voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line v...

Page 13: ...nside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation L...

Page 14: ...tify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature 11 Indicates the UPS is working in bypass mode the load is d...

Page 15: ...eaker or protective components to the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB...

Page 16: ...the output sockets to complete connection Use one cord for every 10A load Model No Output Socket pcs 1K L 3 IEC type 2K L 6 IEC type 3K L 4 IEC type The wiring configuration is shown as the following...

Page 17: ...e the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it...

Page 18: ...ding value after the right values are selected on the LCD panel and the UPS is turn on by pressing the ON Button The UPS would turn to bypass mode in several seconds after Bypass Enable is selected an...

Page 19: ...turn it off first 5 Remove the small cover of terminal block prepare the battery cable which should be able to carry the current of 30A for 1KVA 22A for 2KVA 33A for 3KVA the cross section area shoul...

Page 20: ...loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc The No output m...

Page 21: ...lity power the battery the UPS output and the load could be displayed The word of LINE indicates the inverter of the UPS is working The operating mode code of the UPS is 2 21 battery mode code of the...

Page 22: ...same as battery mode but High and Low would not be shown unless the input line voltage is higher or lower than the SPEC range during the time of battery test The The Battery mode 19 If output overload...