background image

 

-16- 

5.7 Audible alarm mute function:   

If the alarm is too annoying in battery mode, yo u may press “I” button 

continuously for more than 1 second to clear it. Moreover, the alarm 

will be enabled when the battery is low to remind you to shutdown the 

load soon. 

If the alarm is too annoying in bypass mode, you may press “ “button 

continuously  for  more  than  1  second  to  clear  it.  The  action  doesn’t 

affect the warning and fault alarm. 

5.8 Operation procedure of external battery for long backup 

time model (“

L

” model) 

(1)  Use the battery pack  with voltage: 36VDC for 1KL (3 pcs of 12V 

batteries),  96VDC  for  2KL/  3KL  (8  pcs  of  12V  batteries). 

Connection of batteries more than or less than required will cause 

abnormality or permanent damage. 

(2)  One hard wiring type battery terminal on the rear panel is used for 

connecting the battery pack. 

(3)  The  battery  connection  procedure  is  very  important.  Any 

incompliance may  result in the  risk  of electric  shock.  Therefore, 

the following steps must be strictly complied with. 

(4)  Make sure the  mains input is cut off, if there is  a battery breaker 

then turn it off first. 

(5)  Remove  the  small  cover  of  terminal  block,  prepare  the  battery 

cable which should be able to carry the current of >30A for 1KVA, 

>22A for 2KVA, >33A for 3KVA, the cross section area should be 

great  than  4

  mm

for  all  model.  And  battery  wire  color  is 

recommended as following: 

 

GND 

 

Red wire 

Green/Yellow wire 

Black wire 

(6)  The red  wire is  connected to the  "+"  terminal  of the battery.  The 

 

-23- 

2)   It is attentio n that the transfer time of UPS output from ECO mode 

to battery mode is less than 10ms. But it is still too long for some 

sensitive load. 

6.7 Converter mode 

In converter mode, on LCD display, the mode code is “6”. 

The UPS would free run with fixed output frequency (50Hz or 60Hz) 

in  converter  mode.  Once  the  mains  is  loss  or  abnormal,  the  UPS 

would transfer to battery mode and the load is supplied continuously 
by the battery. 

1)  It  could  be  enabled  through  the  LCD  setting  or  the  software 

(Winpower, etc.). 

2) The load should be derating to 60% in converter mode. 

6.8 Abnormal mode 

In  abnormal  mode  such  as  Bus  fault  etc.,  the  corresponding  fault 

code  would  be  shown  to  indicate  the  operating  mode  of  the  UPS. 

And some  warning  words could also be shown, for example “short!” 

would  be  shown  when  the  load  or the UPS  output  is short and  the 
UPS is in inverter fault mode.   

 

 

 

 

Summary of Contents for TAC-HV1K

Page 1: ...fo MarusonUSA com Copyright 2012 All Rights Reserved Maruson is a registered trademark ofMaruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respective own...

Page 2: ...scription 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function...

Page 3: ...9 1 Operation 31 9 2 Storage 31 9 3 Battery Replace 31 10 Technical Data 32 10 1 Electrical specifications 32 10 2 Operating Environment 32 10 3 Typical backup time Typical values at 25 C in minutes 3...

Page 4: ...t sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip...

Page 5: ...remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal b...

Page 6: ...carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are...

Page 7: ...the room where it is ventilated and dry 35 12 Software Free Software Download WinPower WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control you...

Page 8: ...tion I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 In...

Page 9: ...urself with them and understand their meaning 33 10 3 Typical backup time Typical values at 25 C in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 10 4 Dimensions and weights Model No Dimen...

Page 10: ...uninterruptible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers The double converter principle eliminates all...

Page 11: ...ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hour...

Page 12: ...Indicates the input Line voltage value which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line v...

Page 13: ...nside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation L...

Page 14: ...tify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature 11 Indicates the UPS is working in bypass mode the load is d...

Page 15: ...eaker or protective components to the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB...

Page 16: ...the output sockets to complete connection Use one cord for every 10A load Model No Output Socket pcs 1K L 3 IEC type 2K L 6 IEC type 3K L 4 IEC type The wiring configuration is shown as the following...

Page 17: ...e the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it...

Page 18: ...ding value after the right values are selected on the LCD panel and the UPS is turn on by pressing the ON Button The UPS would turn to bypass mode in several seconds after Bypass Enable is selected an...

Page 19: ...turn it off first 5 Remove the small cover of terminal block prepare the battery cable which should be able to carry the current of 30A for 1KVA 22A for 2KVA 33A for 3KVA the cross section area shoul...

Page 20: ...loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc The No output m...

Page 21: ...lity power the battery the UPS output and the load could be displayed The word of LINE indicates the inverter of the UPS is working The operating mode code of the UPS is 2 21 battery mode code of the...

Page 22: ...same as battery mode but High and Low would not be shown unless the input line voltage is higher or lower than the SPEC range during the time of battery test The The Battery mode 19 If output overload...

Reviews: