Maruson | Tacoma 1KVA-3KVA User Manual
10
Figure 3 - Standby Mode
3.2.3.
Bypass Mode
In Bypass Mode, power is directly routed from the mains power to connected
equipment, bypassing internal converters and without regulation. If the controller
detects the mains is abnormal, it will shut off the output to protect the load.
The “bYPA” code status and beep once every 2 minutes indicates the UPS is
working Bypass Mode. Information about the utility power, the battery level, the
UPS output and the load level will be displayed.
Note:
If mains power fails while in Bypass Mode, the UPS
will not
switch over to
Battery Mode. Connected equipment will not have battery backup protection in
this mode, or be protected from power surge and sags.
Figure 4 - Bypass Mode
3.2.4.
Battery Mode
In Battery Mode, power to connected equipment is supplied by battery power
(DC/DC) to the inverter (DC/AC) if mains power fails. When the mains input
recovers, the UPS will then automatically transfer to Line Mode.
The “bATT” code and alarm beep every 4 seconds indicating the UPS is in
Battery Mode.
If the “ON” button on the front panel is pressed while in this mode
for more than 1 second, the alarm will temporarily mute.
Press the “ON” button