Maruson | Tacoma 1KVA-3KVA User Manual
26
EPO
EPO function is
active.
Connect the EPO switch to disable this function and ensure the
connection is secure. If connected to EPO cable, check if EPO
cable needs to be replaced. Replace with one no more than
350 feet or has a resistance greater than 10 ohms.
bLOW
Batteries
disconnected.
Check the battery connections are properly connected.
End of battery
lifespan.
Replace the batteries with the same type and quantity. All
batteries should be replaced at the same time.
HIGH
Battery over
voltage or
charger failed.
Check the charger output, battery input.
5.2.
LCD FAULT CODE
Fault Code Possible Cause Action
SHOR
Output short
circuit occurred
Remove all equipment. Turn off the UPS. Check whether the
output of UPS and equipment have short circuited. Make sure
the short circuit is removed, and the UPS has no internal
faults before turning on again.
INVL
Internal voltage
too low.
Internal fault. Contact your local authorized dealer or
Maruson.
INVH
Inverter voltage
too high.
Inverter voltage is too high. Contact your local authorized
dealer or Maruson.
ISFT
Inverter failed.
Internal fault. Contact your local authorized dealer or
Maruson.
OVLd
Overload
Remove non-critical loads until total capacity is within UPS
capacity range.
OVTP
Internal
temperature too
high.
Check whether the UPS is overloaded, the air vents are
blocked, a fan has failed, or if the ambient temperature is over
104
F / 40
C. Remove any restrictions around the UPS. Clear
the vents and remove any equipment that is causing an
overload. Allow the UPS to cool down for at least 15 minutes
before restarting the UPS.
bUSH
Bus voltage too
high.
Internal fault. Contact your local authorized dealer or
Maruson.
bSFT
Internal fault.
Contact your local authorized dealer or Maruson.
Note:
When the UPS fails, the Fault/Warning icon will appear on the LCD and
backlight will change to red while the alarm beeps continuously.
Note:
When the UPS detects a fault, it will stop the power conversion of mains
and battery.
5.3.
ADDITIONAL TROUBLESHOOTING CONDITIONS
Condition
Possible Cause
Action
UPS not supplying
power to connected
equipment
UPS is in Standby
Mode.
Change UPS to Line Mode.
EPO switch is open.
Check the back of the UPS EPO tab to
ensure it is securely in place. If this is