Maruson | Tacoma 1KVA-3KVA User Manual
29
Note:
Check the battery voltage rating marked on the rear panel before
replacing any batteries. Using the wrong battery voltage may cause
permanent damage of the UPS & EBB.
7.
TRANSPORTION, STORAGE, AND DISPOSAL
7.1.
TRANSPORTATION
Please transport the UPS only in the original packaging with the included foam
inserts. Disconnect internal batteries for transportation.
7.2.
STORAGE
If the UPS or external battery banks will be stored for an extended time, make
sure to fully charge the UPS before storing in a dry, dust free ventilated room
away from direct sunlight. Recharge the UPS and EBB batteries every 3 months
to maintain the battery lifespan. If using the UPS after storage, allow the UPS to
charge for at least 10 hours before use. Storage temperature should be between
5°F to 113°F (5°C to 45°C).
7.3.
DISPOSAL
•
Contact your local recycling or hazardous waste center for information on
proper disposal of spent batteries and waste electric or electronic equipment
(WEEE).
•
This product uses lead-acid batteries that are considered hazardous waste
material and should be disposed of at a local recycling center for batteries or
in accordance to local regulations. Do not dispose batteries with regular
waste. Never dispose batteries in a fire. Batteries may explode. Do not open
or mutilate the batteries. Released electrolyte is harmful to the skin and eyes.
And may be toxic.
•
The packaging that came with this product should be recycled.
8.
PRODUCT SPECIFICATIONS
8.1.
TECHNICAL SPECIFICATIONS*
Model
TAC-LV1K
TAC-LV2K
TAC-LV3K
Capacity
1000VA / 900W
2000VA / 1800W
3000VA / 2700W
Input
Power System
Single-phase
Current (Max.)
10A
20A
30A
Voltage Range
85 - 150Vac @ full load / 55 - 150Vac @ half load
Frequency Range** 50Hz system: 46
– 54Hz / 60Hz system: 56 – 64Hz
Input Power Factor
≧
0.97 @ full load
Output
Power System
Single-phase