EBM installation is similar with UPS, details please refer to below.
It is recommended to place EBM modular to UPS’s left side.
It is recommended to place EBM modular to UPS’s left side.
3.4 Power cables connection
This chapter introduces how to wiring AC IN/OUT cable to UPS in difference mode, and
UPS connecting with EBM.
3.4.1 Input /Output wiring specifications
Recommended protective devices and cable cross-sections
Recommended upstream protection
UPS power rating
Upstream circuit breaker
6000VA
D curve – 63A
10000VA
D curve – 100A
to UPS Normal AC / Bypass AC source
G N(L2) L1
Read the Safety instructions page 3 regarding backfeed protection requirements.
Recommended cable cross-sections
N(L2)