18
3.4.3 Wiring with external battery modular (EBM) (DC source to UPS)
1. Be sure to disconnect the battery cable from the EBM before connecting the battery
terminals of the UPS
2. Make sure the UPS is completely off before connecting or disconnecting the EBM.
3. Before connecting the EBM, make sure that the number of battery sections and
capacity are the same as LCD setting.
4. Do not reverse the polarity of the external battery.
•
Connect with user’s own EBM:
Connect EBM to UPS with ‘Battery cable’ (optional configured).
Note:
1. If additional battery cable needed for installation, it must follow cable specification
and the maximum length of battery cable 10 meters for application.
2. If a length of battery cable over 10 meters requests, please contact
distributors/agents for details.