Safety of persons
RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate
the UPS and check for hazardous voltage upstream and downstream during lockout-
tagout operation. Terminal blocks may be energized even if the system is disconnected
from the AC power source.
Dangerous voltage levels are present within the system. It should be opened exclusively
by qualified service personnel.
The system must be properly grounded.
The battery supplied with the system contains small amounts of toxic materials. To avoid
accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or
battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may
be very high.
Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).
Product safety
The UPS connection instructions and operation described in the manual must be followed
in the indicated order.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection for :
63A rating, for 6kVA models,
100A rating, for 10kVA models
•
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The unit
can be disconnected from AC power source by opening this circuit breaker.
An additional AC contactor is used for backfeed protection and must comply with IEC/EN
62040-1 (the creep age and clearance distances shall meet the basic insulation
requirements for pollution degree 2).