45
Conditions
Possible cause
Action
BUS Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F025
Indicates that the BUS could not
soft start successfully
Contact your service representative
Inv Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F032
Indicates that the UPS get invert
over voltage fault
The UPS transfers to Bypass mode if
supporting the load
Inv Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F033
Indicates that the UPS get
inverter under voltage fault
The UPS transfers to Bypass mode if
supporting the load
Inv Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F034
Indicates that the inverter could
not soft start successfully
Contact your service representative
Charger Fail
Fault (Red) LED is flash
1 beep every 1 second
Code: A015
Indicates that the UPS has
confirmed the charger has failed
The UPS turns off the charger until
the next power recycle. Contact your
service representative
Battery Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F016
Indicates that the battery voltage
is too high
The UPS will turn off the charger
until the battery voltage is normal
Negative power Fault
Fault (Red) LED is On.
Beep continuous.
Code: F0E1
In parallel system
,
power of UPS
is negative
Redundancy mode
,
the fault UPS
turn to fault mode without output
Increase mode
,
UPS1& UPS2 turn
to fault mode
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: F0E2
In parallel system
,
parallel cable
disconnect
Disconnect parallel cable one turn to
fault mode
Parallel system battery
status
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E6
UPS1 connect battery
,
UPS2
without battery
Check battery connect status