background image

18 

 

 

6. Specifications 

 

MODEL 

ULT-W1K(L) 

ULT-W2K(L) 

ULT-3K(L) 

CAPACITY* 

1000 VA / 800 W 

2000 VA / 1600 W 

3000 VA / 2400 W 

INPUT 

Voltage 

Range 

Low Line Transfer 

85VAC/75VAC/65VAC/55VAC± 5% or 160VAC/140VAC/120VAC/110VAC± 5%   

(Ambient Temp.<35

0

C) 

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

Low Line Comeback 

95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ±  5 %   

(Ambient Temp.<35

0

C) 

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

High Line Transfer 

145 VAC ±  5 % or 300 VAC ±  5 %   

High Line Comeback 

140 VAC ±  5 % or 290 VAC ±  5 %   

Frequency Range 

40Hz ~ 70 Hz 

Phase 

Single phase with ground 

Power Factor 

 0.99 @ nominal voltage (input voltage) 

OUTPUT 

Output voltage 

100/110/115/120/127VAC or 200/208/220/230/240VAC 

AC Voltage Regulation   

± 1% (Batt. Mode) 

Frequency Range   

47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) 

Frequency Range (Batt. Mode) 

50 Hz ±  0.25 Hz or 60Hz ±  0.3 Hz 

Overload 

Ambient Temp.<35

0

105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when 

the utility is normal 

110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the 

utility is normal 

>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the 

utility is normal 

Current Crest Ratio 

3:1 

Harmonic Distortion 

  3 % THD (linear load); 

  6 % THD (non-linear load) 

Transfer 

Time 

AC Mode to Batt. Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

88% 

89% 

90% 

Battery Mode 

83% 

87% 

88% 

BATTERY 

Standard 
Model 

Battery Type 

12 V / 9 AH 

12 V / 9 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% capacity (Typical) 

Charging Current   

1.0 A (max.) 

Charging Voltage   

27.4 VDC ±  1% 

54.7 VDC ± 1% 

82.1 VDC ± 1% 

Long-run 

Model(L)* 

Battery Numbers 

Charging Current   

1.0A/2.0A/4.0A/6.0 A 

Charging Voltage 

27.4 VDC ±  

1% 

41.0VDC ±  

1% 

54.7 VDC 

± 1% 

82.1VDC 

± 1% 

109.4VDC 

± 1% 

82.1 VDC 

± 1% 

109.4VDC 

± 1% 

PHYSICAL 

Standard 

Model 

Dimension, D X W X H   

282 X 145 X 220 (mm) 

397 X 145 X 220 (mm) 

421 X 190 X 318 (mm) 

Net Weight (kgs) 

9.8 

17 

27.6 

Long-run 

Model* 

Dimension, D X W X H   

282 x 145 x 220 (mm) 

397x 145 x 220(mm) 

Net Weight (kgs) 

4.1 

4.1 

6.8 

6.8 

6.8 

7.4 

7.4 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

*Long-run model is only available in 200/208/220/230/240VAC systems. 
** Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 100/200/208VAC. 

*** Product specifications are subject to change without further notice. 
 

Summary of Contents for ULT-3K

Page 1: ...ale Avenue City of Industry California 91748 U S A Tel 1 626 912 8388 Fax 1 626 912 8680 Toll Free 1 888 MARUSON E Mail Info MarusonUSA com Website www MarusonUSA com All trademarks are the property o...

Page 2: ...s 2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 10 3...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...thing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC T...

Page 6: ...ersal Type 3KL India Type IEC Type Schuko Type Universal Type 1 AC input 2 Input circuit breaker 3 USB communication port 4 RS 232 communication port 5 SNMP intelligent slot option 6 External battery...

Page 7: ...for 2K model Step 3 UPS output connection For socket type outputs simply connect devices to the outlets For terminal type input or outputs please follow below steps for the wiring configuration a Remo...

Page 8: ...the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability duri...

Page 9: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Page 10: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS...

Page 11: ...twice every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss...

Page 12: ...voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac Default 127 presents output voltage is 1...

Page 13: ...the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Inte...

Page 14: ...mitation setting Interface Setting Parameter 3 Set up backup time on battery mode for general outlets 0 999 setting the backup time in minutes from 0 999 for general outlets on battery mode 0 When set...

Page 15: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 16: ...ltage high 12 x Charger failure 45 x Inverter voltage Low 13 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c...

Page 17: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Page 18: ...up time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defe...

Page 19: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 20: ...t Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 8...