3-5. UPS Setting
Parameter 1
Parameter 2
There are two parameters to set up the UPS.
P
arameter 1: It’s for program alternatives.
Refer to below table.
Parameter 2 is the setting options or values
for each program.
⚫
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 120Vac models, you may choose the following output voltage:
100:
presents output voltage is 100Vac
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
125:
presents output voltage is 125Vac
⚫
02: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
⚫
03: Programmable outlets setting
Interface
Setting
Parameter 2:
Set up backup time limits for programmable outlets.
0-999:
setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on battery
mode. (Default: 999)
⚫
04: Site fault detection enable/disable
Interface
Setting
Parameter 2:
Enable or disable site fault detection. You may choose
the following two options:
ENA:
Site fault detection enable(Default for UL models)
DIS:
Site fault detection disable
⚫
05: Autonomy limitation setting
Interface
Setting