14
Parameter 2:
Set up backup time on battery mode for general outlets.
0-999:
setting the backup time in minutes from 0-999 for general outlets
on battery mode.
DIS:
Disable the autonomy limitation and the backup time will depend
on battery capacity. (Default)
Note:
When setting as “0”, the backup time will be only 10 seconds.
⚫
07: EPO logic setting
Interface
Setting
Parameter 2:
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in open status.
AC:
Active Close. When AC is selected as EPO logic, it will activate
EPO function with Pin 1 and Pin 2 in close status.
⚫
08: Input Waveform Sensitivity setting
Interface
Setting
Parameter 2:
Set Input Waveform Sensitivity.
St1
: Input voltage waveform detection is highly sensitive. (Default)
St2
: Input voltage waveform detection is middle sensitive.
St3
: Input voltage waveform detection is low sensitive. (use with
generators or Step wave input)
⚫
09: LCD display backlight setting
Interface
Setting
Parameter 2
: Set up the working mode for the LCD display
backlight.
Aon
: LCD display backlight is on all the time.
Aut
: LCD display backlight will be off after pressing the
buttons 60seconds. (Default)
⚫
00: Exit setting
Interface
Setting
Exit the setting mode.
3-6. Operating Mode Description
Operating mode
Description
LCD display
ECO mode
When the input voltage is within voltage regulated range,
UPS will power the output directly from the mains. ECO is
an abbreviation of Efficiency Corrective Optimizer. In this
mode, when battery is fully charged, the fan will stop
working for energy saving.