6. Specifications 

 

MODEL 

1K   

1.5K   

2K 48V 

2K 76.8V 

3K   

CAPACITY 

1000VA/900W 

1500VA/1350W 

2000VA/1800W 

1920VA/1920W 

3000VA / 2700W 

INPUT 

Acceptable Voltage Range 

75-117/81-134/86-139/89-145/102-152 VAC 

Frequency Range 

60/50 Hz (auto sensing) 

OUTPUT 

Voltage Regulation (AC Mode)* 

100*(-13%/+10%)/110(-15%/+10%)/115(-14%/+10%)/120(-14%/+10%)/125(-11%/+11%) VAC 

Voltage Regulation (Batt.Mode) 

100/110/115/120/125 VAC ±1.5%(before low battery alarm) 

Frequency Range (Batt.Mode) 

60 Hz or 50 Hz ± 0.1 Hz 

Current Crest Ratio 

3:1 

Harmonic Distortion 

2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) 

Transfer Time 

Typical 2-6 ms, 10ms max.                         

Waveform (Batt.Mode) 

Pure Sine Wave 

Over Load Capacity 

103% to 120% Alarm warning with shutdown after 5 minutes (1minutes @ battery mode) 

120% to 150% Alarm warning with shutdown after 10 seconds 

150% and greater Shutdown UPS Immediately 

EFFICIENCY 

AC Mode 

96.7% 

Buck & Boost Mode 

93%

 

for 120VAC models 

Battery Mode@75%load 

88%   

90% 

90.5% 

BATTERY 

Battery Type   

LIFE-247500 

LIFE-485000 

LIFE-722500 

Battery Number 

Charging Voltage 

28 VDC ± 1% 

52.5 VDC ± 1% 

84 VDC ±1% 

Recharge Time 

3 hours recover to 100% capacity 

PROTECTION 

Full Protection 

Overload, short, discharge, and overcharge protection 

PHYSICAL RT 

Unit Dimensions, W x D x H(mm) 

410 X 438 X 88 

510 X 438 X 88 

630 X 438 X 88 

Unit Weight (kg) 

10.5 

12.6 

17.1 

16.3 

22.3 

OPERATION ENVIRONMENT 

Humidity & Temperature 

20-90 % RH @ 0-40°C (non-condensing) 

Elevation 

Up to 2,000m

 @ 0-40°C without derating. 

Ambient temperature will require derating of 5 °C for each additional 500 m in altitude. 

Noise Level 

Less than 45dB@Line mode, Less than 55dB@Battery mode 

MANAGEMENT 

Smart RS-232/USB 

Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

* Derate capacity to 85% of capacity when the output voltage is adjusted to 100/200VAC. 

**Product specifications are subject to change without further notice. 

 
 

 

Summary of Contents for Ultima LiFe RT 1.5K

Page 1: ...Maruson Technology Corporation 16050 Kaplan Ave City of Industry CA 91744 U S A Tel 1 714 870 6888 Fax 1 714 870 4888 Toll Free 1 888 MARUSON Website www MarusonUSA com E Mail Info MarusonUSA com All...

Page 2: ...principle 5 2 3 Install The UPS Only for RT Models 5 2 4 Setup The UPS 6 2 5 Battery Replacement 8 3 Operations 10 3 1 Button Operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 11 3 4 LCD Display Wordin...

Page 3: ...laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them The UPS can be operated by any individuals with no previous experience Connect the UPS sy...

Page 4: ...tage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the AC power source before servicing the battery Only pe...

Page 5: ...d if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular in...

Page 6: ...RT Model 1K 1 5K NEMA Type 2K NEMA Type 3K NEMA Type 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 N...

Page 7: ...install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front panel Connect the AC input and re connect battery wires Put the front panel back to the u...

Page 8: ...full load The highest working temperature requirement for UPS operation is 50 C The battery can not be charged when temperature is above 50 C 3 It s required to maintain maximum altitude of 1000m to k...

Page 9: ...critical devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication port USBport RS 232 port Intelligent slot To allow for unattended UPS shutdown st...

Page 10: ...r as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is sounding every 2 seconds it s time to replace...

Page 11: ...ll out the battery box by removing two screws on the front panel Step 4 Step 5 Step 6 After replacing the batteries put the battery box back to original location and screw it tightly Re connect the ba...

Page 12: ...t frequency battery voltage battery capacity ambient temperature output voltage output frequency load current and load percent Setting mode Press and hold this button for 3 seconds to enter UPS settin...

Page 13: ...outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates charging status Indicates the UPS is working in boost mode Indicates t...

Page 14: ...able ESC Escape AO AC Active Open Close ST1 2 3 Input Waveform Sensitivity 1 2 3 AUT AON Automatic Always on OK OK ON ON BL Battery Low OL Over Load NC Battery No Connect OC Over Charge SF Site Fault...

Page 15: ...125Vac 02 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 03 Programma...

Page 16: ...ting Parameter 2 Set Input Waveform Sensitivity St1 Input voltage waveform detection is highly sensitive Default St2 Input voltage waveform detection is middle sensitive St3 Input voltage waveform det...

Page 17: ...PS will backup power from battery and alarm is sounding every 10 seconds Standby mode UPS is powered off and no output supply power but still can charge batteries Fault mode When a fault has occurred...

Page 18: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Page 19: ...sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alar...

Page 20: ...d battery voltage is less than 10V PC Contact your dealer 5 Storage and Maintenance 5 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambien...

Page 21: ...AC Mode 96 7 Buck Boost Mode 93 for 120VAC models Battery Mode 75 load 88 90 90 5 BATTERY Battery Type LIFE 247500 LIFE 485000 LIFE 722500 Battery Number 1 1 2 2 3 Charging Voltage 28 VDC 1 52 5 VDC...

Reviews: