sides of the UPS for heat dissipation and easy-maintenance.   

 

Step 1: UPS input connection 

Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. 

 

 

For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug 

is a NEMA 5-15P for 1K and 1.5K models, NEMA 5-20P for 2K model and NEMA L5-30P for 3K 
model.

 

Note:

 Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the 

UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section). 

Please also check if there is a circuit breaker against overcurrent and short circuit between the 
mains  and  AC  input  of  the  UPS  for  safety  operation.  The  recommended  protection  value  as 
following: 

 

For 100/110/115/120/127VAC models: 15A for the 1K and 1.5K models, 20A for 2K model and 
30A for 3K model. 
 

Step 2: UPS output connection 

There two kinds of outputs: programmable outlets and general outlets. Please connect non-critical 
devices to the programmable outlets and critical devices to the general outlets. During power 
failure, you may extend the backup time to critical devices by setting shorter backup time for 

non-critical devices.   
 

Step 3: Communication connection 

Communication port:

 

USB port 

RS-232 port 

Intelligent slot

 

 

 

 

To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of 
communication cable to the USB/RS-232 port and the other to the communication port of your PC. 

With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS 
status through PC. 
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing 
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring 

options.   

 

Step 4: Network connection 

Network/Fax/Phone surge port 

 

Connect a single modem/phone/fax line into surge-

protected “IN” outlet on the back panel of the 

UPS unit. Connect from “OUT” outlet to the 

equipment with another modem/fax/phone line cable.

 

 

Step 5: Disable and enable EPO function 

This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin 1 

and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To 
activate EPO function, remove two screws on EPO port and green connector will be removed. 

Note: 

The EPO function logic can be set up via LCD setting. Please refer to program 7 in UPS 

setting for the details.

 

Summary of Contents for Ultima LiFe RT 1.5K

Page 1: ...Maruson Technology Corporation 16050 Kaplan Ave City of Industry CA 91744 U S A Tel 1 714 870 6888 Fax 1 714 870 4888 Toll Free 1 888 MARUSON Website www MarusonUSA com E Mail Info MarusonUSA com All...

Page 2: ...principle 5 2 3 Install The UPS Only for RT Models 5 2 4 Setup The UPS 6 2 5 Battery Replacement 8 3 Operations 10 3 1 Button Operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 11 3 4 LCD Display Wordin...

Page 3: ...laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them The UPS can be operated by any individuals with no previous experience Connect the UPS sy...

Page 4: ...tage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the AC power source before servicing the battery Only pe...

Page 5: ...d if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular in...

Page 6: ...RT Model 1K 1 5K NEMA Type 2K NEMA Type 3K NEMA Type 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 N...

Page 7: ...install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front panel Connect the AC input and re connect battery wires Put the front panel back to the u...

Page 8: ...full load The highest working temperature requirement for UPS operation is 50 C The battery can not be charged when temperature is above 50 C 3 It s required to maintain maximum altitude of 1000m to k...

Page 9: ...critical devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication port USBport RS 232 port Intelligent slot To allow for unattended UPS shutdown st...

Page 10: ...r as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is sounding every 2 seconds it s time to replace...

Page 11: ...ll out the battery box by removing two screws on the front panel Step 4 Step 5 Step 6 After replacing the batteries put the battery box back to original location and screw it tightly Re connect the ba...

Page 12: ...t frequency battery voltage battery capacity ambient temperature output voltage output frequency load current and load percent Setting mode Press and hold this button for 3 seconds to enter UPS settin...

Page 13: ...outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates charging status Indicates the UPS is working in boost mode Indicates t...

Page 14: ...able ESC Escape AO AC Active Open Close ST1 2 3 Input Waveform Sensitivity 1 2 3 AUT AON Automatic Always on OK OK ON ON BL Battery Low OL Over Load NC Battery No Connect OC Over Charge SF Site Fault...

Page 15: ...125Vac 02 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 03 Programma...

Page 16: ...ting Parameter 2 Set Input Waveform Sensitivity St1 Input voltage waveform detection is highly sensitive Default St2 Input voltage waveform detection is middle sensitive St3 Input voltage waveform det...

Page 17: ...PS will backup power from battery and alarm is sounding every 10 seconds Standby mode UPS is powered off and no output supply power but still can charge batteries Fault mode When a fault has occurred...

Page 18: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Page 19: ...sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alar...

Page 20: ...d battery voltage is less than 10V PC Contact your dealer 5 Storage and Maintenance 5 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambien...

Page 21: ...AC Mode 96 7 Buck Boost Mode 93 for 120VAC models Battery Mode 75 load 88 90 90 5 BATTERY Battery Type LIFE 247500 LIFE 485000 LIFE 722500 Battery Number 1 1 2 2 3 Charging Voltage 28 VDC 1 52 5 VDC...

Reviews: