3-7-2-2. Control items
NOTE 1: Usually, all these four items could be seen on this interface except for “Para Unlock”. “Para Unlock”
appears when and only when parallel communication failure is happening.
NOTE 2: “Turn On” will be displayed if UPS is not turned on; “Turn Off” will be displayed if UPS is turned on;
In the general situation, these items will not be displayed in the same time or in all operation modes.
1)
Turn On/Turn Off
This item is for turning on/off the UPS;
a)
On Bypass mode, it will display “Turn On”, if it is selected and confirmed, the UPS will transfer to line
mode or converter mode or ECO mode or battery mode according to the setting and input status.
→
→
NOTE: you could turn on UPS by pressing the “ON/ENTER” button in home page, no necessary enter
into this control menu.
b)
On line mode or converter mode or ECO mode or battery mode, it will display “Turn Off”, if it is
selected and confirmed, the UPS will transfer to bypass mode or shutdown.
→
→
NOTE: you could turn off UPS by pressing the “OFF/ESC” button in home page, no necessary
enter into this control menu.
2)
Battery Test
This item is to instruct the UPS enter battery test mode, it is for checking that if the UPS could work well
in battery mode and testing the battery performance. This item could be shown in all modes but it would not
work in Battery/Fault/Eco mode and also related hint will be shown at the same time.