25
2) ECO setting
(only available or effective on bypass mode)
Interface
Description
1.
Status
Enable:
Enable ECO Function
Disable:
Disable ECO Function
If ECO function is disabled, voltage range and frequency range for
ECO mode still can be set, but it is meaningless unless the ECO
function is enabled.
2.
HighLoss V:
High voltage point in ECO mode. The setting range
is from +5% to +10% of the nominal voltage.
3.
LowLoss V:
Low voltage point in ECO mode. The setting range is
from -5% to -10% of the nominal voltage.
4.
HighLoss F:
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
5.
LowLoss F:
Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
3) Output setting
(only available or effective on bypass mode)
Interface
Description
1.
Volt:
208:
Presenting the rated output voltage with 208Vac
220:
Presenting the rated output voltage with 220Vac
230:
Presenting the rated output voltage with 230Vac
240:
Presenting the rated output voltage with 240Vac
2.
Freq:
50Hz:
The output frequency is setting for 50Hz.
60Hz:
The output frequency is setting for 60Hz.
ATO:
If selected, output frequency will be decided according to
the latest normal utility frequency. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the
output frequency will be 60.0Hz. ATO is default setting.
3.
CVCF:
To decide whether or not converter mode is activated.
Enable:
The output frequency will be fixed at 50Hz or 60Hz
according to setting of “Freq”. The input frequency could be from
46Hz to 64Hz.
Disable:
The output frequency will synchronize with the input
frequency within 46~54 Hz for 50Hz system or within 56~64 Hz
for 60Hz system.
NOTE: CVCF means Constant Voltage and Constant Frequency, it
represents converter mode.
4) Battery setting
(available on all operation modes)
Interface
Description
1.
Dischg Protect:
1.1
Enable:
Battery discharge protection function is enabled. When UPS
have been continuously working in “battery/battery test mode”, the
UPS will automatically shut down when the running time set by option
1.2 below is up;
Disable:
Battery discharge protection function is disabled.
1.2
000~999:
The maximum discharge time ranging from 0 to 999mins.