26
UPS will shut down to protect battery after backup time arrives when
the “Dischg Protect” is enabled. If “Dischg protect” is disabled, then
this setting does not make sense whatever the setting is; The default
value for this setting is 990mins.
2. Batt Test Type:
2.1 Short Time:
Battery test will last for constant 10 seconds;
2.2 Long Time:
Battery test could last for longer time, which is
able to be adjusted within 01~99 minutes;
2.3 Till Batt Low:
Battery test will not stop until battery
voltage is low.
5) Calibration
Interface
Description
1.
Batt:
Calibrate the battery voltage measurement; the calibration
range is from 0V to 5.7V, the default value is 0V. It is available on
all operation modes.
2.
Inv:
Adjust the inverter output voltage; the adjustable range is
from 0V to 6.4V, the default value is 0V. It is only available in line
/ battery / converter mode;
3.
Chg:
Adjust the Charger output voltage; the adjustable value is
from 0V to 6.9V, the default value is 0V. It is only available in
bypass / line / ECO /converter mode.
(NOTE: Before making charger output voltage adjustment, be
sure to disconnect all batteries first to get the accurate charger
voltage; Be careful that the adjustment should be suitable to
battery specifications, or the battery maybe destroyed.)