6) Other settings
(available on all operation modes)
Interface
Description
Hot standby:
Enable:
Hot standby function is enabled. It means that the current
UPS is set to be host of hot standby system, and it will automatically
restart after AC recovery even without battery connected.
Disable:
Hot standby function is disabled. The UPS is running at
normal mode and can’t restart without battery.
Disable is default setting.
Backup Time Parameters Setting:
Batt Groups:
Set the number of battery group ranging from 1 to 6.
The default value is 1 group
;
Batt Cap:
Set the battery capacity such as 7AH, 9AH, 10AH, 12AH,
17AH, 26AH, 40AH, 65AH, 100AH and so on. The default value is 9AH.
Factor:
Calibrate the displayed backup time by adjusting this
multiplier factor. The formulation is listed below:
Displayed backup time=Original calculated backup time× Multiplier
factor
The value of default factor is 1.0, and it ranges from 0.5 to 2.
These parameters are for the battery backup time calculation