3
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper
precautions.
a) Remove watches, rings, or other metal objects
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source prior to connecting or disconnecting battery terminals.
f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source
from ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded
supply circuit).
• Do not dispose of the batteries in a fire. Do not open the UPS or batteries. The batteries must be rightly
deposed according to local regulation.
• Do not short or bridge the battery terminals with any object.
• Unplug and turn off the UPS before performing battery replacement.
• Battery replacement should be performed only by authorized service personnel using the same number
and type of batteries (Sealed Lead-Acid). Use tools with insulated handles. The batteries are recyclable.
• Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be
toxic.
• Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply.
1-5. Standards
* Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (4th Edition)
Safety Markings : TUV, cTUVus, CE
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning:
This is a product for commercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevent disturbances.