6
Marvair ComPac Installation & Operation Manual
12/2017 Rev.16
1.4
Air Flow, Weights and Filter Sizes
Complete electrical and performance specifications and dimensional drawings are in the Marvair
ComPac Product Data Sheets.
MODEL
0.10
0.15
0.20
0.25
0.30
0.40
0.50
AVPA/AVHA12
450
420
390
360
AVPA24/AVHA20/24
860
825
810
740
670
AVPA/AVHA30
1100
1050
1000
960
920
810
AVPA/AVHA36
1310
1265
1220
1185
1150
1060
AVPA/AVHA42
1650
1585
1520
1450
1360
AVPA/AVHA48
1900
1830
1760
1700
1620
AVPA/AVHA60
1900
1830
1760
1700
1620
AVPA72
2100
1950
1800
1730
1660
HVEA24
800
785
770
725
680
600
500
HVEA30
1200
1150
1100
1050
1000
900
800
HVEA36
1290
1230
1170
1115
1060
1000
920
HVEA42
1500
1430
1360
1295
1230
1160
1070
HVEA49
1900
1850
1800
1700
1600
1500
1350
HVEA60
1900
1850
1800
1700
1600
1500
1350
HVESA36
1290
1230
1170
1115
1060
1000
920
HVESA42
1500
1430
1360
1295
1230
1160
1070
HVESA49
1900
1850
1800
1700
1600
1500
1350
HVESA60
1900
1850
1800
1700
1600
1500
1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation
of units at a voltage different from the rating point will affect air flow.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL
INCHES
MILLIMETERS
PART NUMBER FILTERS PER UNIT MERV RATING
AVPA/AVHA12 (Non-Economizer)
20 x 10 x 2
508 x 254 x 52
91974
1
7
AVPA/AVHA12 (With Economizer)
22¼ x 6¼ x 2
565 x 159 x 51
80172
1
7
AVPA24/AVHA20/24
25 x 16 x 2
635 x 406 x 52
80137
1
7
AVPA/AVHA30/36 & HVEA24
30 x 16 x 2
762 x 406 x 52
80138
1
7
AVPA/AVHA42/48/60 &
HVEA30/36/42 & HVESA36/42
36½ x 22 x 2
927 x 559 x 52
80162
1
7
AVPA72 & HVEA49/60 & HVESA49/60
18 x 24 x 2
457 x 610 x 52
81257
2
7
Table 2. Return Air Filter Sizes
MODEL
LBS
KG
ComPac Non-Economizer
AVPA/AVHA12
175
79.5
AVPA24/AVHA20/24
275
125
AVPA/AVHA30/36 & HVEA24
355
160
AVPA/AVHA42/48/60 & HVEA30/36 & HVESA36/42
535
245
HVEA49/60 & HVESA49/60
625
284
ComPac With Economizer
AVPA/AVHA12
185
84.1
AVPA24/AVHA20/24
286
130
AVPA/AVHA30/36 & HVEA24
375
170
AVPA/AVHA42/48/60 & HVEA30/36 & HVESA36/42
590
268
HVEA49/60 & HVESA49/60
640
291
Table 3. Shipping Weights for ComPac
1.5 General Operation
Refrigerant Cycle (Cooling Mode)
Marvair ComPac air conditioners use R-410A refrigerant in a conventional vapor-compression refrig-
eration cycle to transfer heat from air in an enclosed space to the outside. A double blower assembly
blows indoor air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled
into gas by heat removed from the air. The warmed refrigerant gas enters the compressor where its