Page 8

Optima 320 Series

2.2  Installation Mounting

EN — These products are heavy. The flange mounting ears are designed to hold the PDU securely 

against the rack mounting rails, but are NOT designed to support the weight of the product 

vertically. The end user is responsible for ensuring the product’s weight is properly supported by the 

rack’s infrastructure (which may require adding support rails).

 

 

FR — Ces produits sont lourds. Les oreilles de montage à bride sont conçues pour maintenir 

solidement l’unité de distribution de l’alimentation contre les rails de montage, mais NE sont 

pas conçues pour soutenir le poids du produit verticalement. Il incombe à l’utilisateur final de 

s’assurer que le poids du produit est correctement supporté par l’infrastructure du bâti (ce qui peut 

nécessiter l’ajout de rails de support).

(A) The mounting ears, highlighted in blue, can be positioned flush with the front, or recessed from the front. They can also 

be flipped (not shown) to mount the rear panel flush or recessed from the rear of the PDU.

(B) The PDU should be supported by rails (not provided). The PDU is too heavy to mount only with the ears.

Optima

Optima

A

B

Summary of Contents for Optima 320 Series

Page 1: ...Optima 320 Series Power Distribution Units Operating Guide and Reference Aug 2022 P N 501058 000 Rev D Optima 3 ON OFF Optima 3 ON OFF ON OFF Optima 3 ON OFF V A ...

Page 2: ...ation FR 4 1 4 Avis de sécurité FR 4 1 5 General Description 5 1 6 Product Models 5 1 7 Product Ratings 6 2 Installation 7 2 1 Installation Notes 7 3 Operation 8 3 1 Startup 8 3 2 Breakers 8 3 3 Digital Meter 8 4 Specifications 9 5 Contact and Support 10 5 1 Repairs 10 5 2 Contact Options 10 5 3 Two Year Warranty 10 ...

Page 3: ... signal cabling Do not open this product as it contains no user serviceable parts inside All service concerns should be directed to Marway Power Solutions If this product is used in a manner which does not comply with this instruction manual the protection provided by the equipment may be impaired All work on connections must be carried out under zero voltage output disconnect and may only be perf...

Page 4: ...s ce produit car il ne contient aucune pièce réparable par l utilisateur Tous les problèmes de service doivent être adressés à Marway Power Solutions Si ce produit est utilisé d une manière non conforme au présent manuel d instructions la protection fournie par l équipement peut être compromise Tous les travaux sur les connexions doivent être effectués sous une tension nulle et ne doivent être eff...

Page 5: ...a steel chassis are designed for fixed mounting within a 1U rack space in an EIA 310 compliant rack enclosure and include removable reversible mounting brackets 1 6 Product Models Marway s Standard Products Catalog includes more detailed tables with exact model number configurations with inlets outlets and options identified Model Inlet Outlet Configuration B back F front Breakers Meter Configurat...

Page 6: ...eptacle count used 320004 320011 100 240 Vac 1ɸ 50 60 Hz 16 A maximum 100 240 Vac 1ɸ 10 A maximum per C13 receptacle 16 A maximum total per unit regardless of receptacle count used 320006 120 Vac 1ɸ 50 60 Hz 24 A continuous 30 A maximum 120 Vac 1ɸ 16 A continuous 20 A max per 5 20R receptacle 16 A continuous 20 A max total per outlet group circuit breaker regardless of receptacle count used 24 A c...

Page 7: ...d for your installation location connect the chassis ground wire to the rack cabinet using an appropriate fastener 3 Optionally connect the appropriate cables between the PDU outlets and the equipment being powered by the PDU This may be done later according to the startup procedures suitable to the end user s equipment and application 4 PDU Main Breaker Ensure the Main Breaker on the front of the...

Page 8: ...our maintenir solidement l unité de distribution de l alimentation contre les rails de montage mais NE sont pas conçues pour soutenir le poids du produit verticalement Il incombe à l utilisateur final de s assurer que le poids du produit est correctement supporté par l infrastructure du bâti ce qui peut nécessiter l ajout de rails de support A The mounting ears highlighted in blue can be positione...

Page 9: ...a main breaker protecting the whole unit and providing on off control for the whole unit When there are two breakers each breaker protects one group of outlets Outlets are organized into identical groups The breaker on the front panel protects the outlets on the front panel and the breaker on the back panel protects the outlets on the back panel The back panel is the one with the inlet connection ...

Page 10: ...tlet group per breaker Regulatory All models certified to UL 62368 1 All models CE marked Environment Operating Temperature 32 F to 122 F Maximum Altitude 6 562 feet Relative Humidity 5 to 85 non condensing Digital Meter some units Volts RMS is measured 2 updated every 15 s Amps RMS is measured 2 updated every 15 s Surge Suppression standard All models except 320001 include a varistor 120 Vac mode...

Page 11: ...ment Marway will repair or exchange at Marway s sole discretion any unit purchased shown to be defective in materials or workmanship when used for its intended purpose This will be done at no charge to the purchaser Purchaser will return unit s at its own expense and only with prior autorization from the factory Instructions will be given by an authorized factory representative at the time an inqu...

Page 12: ...er DC are trademarks of Marway Power Systems Inc All other trademarks are the property of their respective owners Global Support Contacts Web www marway com Email support marway com sales marway com Phone 800 462 7929 7am 5pm PST There may be updates to this documentation at http www marway com docs Marway Power Solutions 1721 S Grand Ave Santa Ana CA 92705 800 462 7929 marway marway com ...