44 | 50
Installation Manual LOGS50 EN_MI_090221
Alarm history memory (HA)
Unit
Min.
Typ.
Max.
Capacity
KB
256
Number of registers (line by variable)
6241
History pages
Nº pag.
8
Duration 3G transmission (HA full)
Minutes
14
Duration in GPRS transmission (HA full)
Minutes
17
Wireless module
EHS6 / EHS8 Wireless 3G HSPA + GPS
Unit
Min.
Typ.
Max.
UMTS number of bands
5
UMTS bands
Mhz
900-1800 / 850-
1900 / 2100
HSDPA Cat. 8 HSUPA Cat. 6
Download data transfer
Mbps
7.2
Upload data transfer
Mbps
5.76
Número de bandas GSM / GPRS
4
Bandas GSM/GPRS
MHz
900-1800 / 850-
1900
GPRS class 12
Transferencia de datos de bajada
Kbps
85.6
Transferencia de datos de subida
Kbps
85.6
Communications ports
Unit
Type
Wireless serial port
BT
Modbus RTU serial port
RS485
cellular module GSM/GPRS/3G
TCP/IP
Analog inputs
Current loop 4-20 / 0-20 mA
Unit
Min.
Typ.
Max.
Number
4
Range
mA
0
20
Range
mA
4
20
Input impedance
Ω
240
Resolution
bit
12
Standard precision
%
0.5
Special precision
%
0.05
Selector position slid upwards.
Voltage mode 0-10 VDC
Unit
Min.
Typ.
Max.
Number
4
Range
V cc
0
10
Input impedance
K Ω
37.5
Resolution
bit
12
Standard precision
%
0.5
Special precision
%
0.05
Selector position slid downwards.