background image

© MASS ELECTRONICS Pty Ltd  2008

Application

The Innotech Micro2000 Series Controllers are designed to be used 

in commercial applications to provide complete control for air 

conditioning systems.

Features

•  LED Display of Temperature and Program functions

•  Control Station fits standard electrical wall plates

•  Four core screened cable simplifies connection between the control 

station and controller

•  Adjustable Proportional Band, Dead Zone, Compressor Restart Time, 

After hours Timer and Setpoint Range

•  Able to operate as 2 cool, 2 electric heating or as reverse cycle heating 

or cooling

•  After Hours function

•  365 Day Battery Backed Real Time Clock

•  Programmable Schedules, 2 schedules per day

•  Programmable Holidays, 20 On/Off Dates

•  Storage of Accumulated After Hours Run Time 

•  All adjustments from the control station

Specifications

Power Supply

•  Voltage:  

 

240VAC ±10% @ 50/60Hz

•  Power Consumption:  

7VA max.

Inputs

•  10k

 Thermistor temperature sensor

•  Digital Input for Switched contact  

 

Outputs

Relay # 1:

Voltage free relay contacts:
Normally Open 240VAC, 16A resistive

240VAC, 6A inductive

Relay # 2, 3:

Voltage free relay contacts:
Normally Open 240VAC, 10A resistive

240VAC, 6A inductive

Relay # 4, 5:

Voltage free relay contacts:
Normally Open 240VAC, 2A resistive

240VAC, 0.5A inductive

Connection Between Controller and Control Station

•  3 way connection via 2 core plus screen cable

Control Station Terminal Identification

•  IN  1   

Temperature Sensor input

•  IN  2   

Digital Input for Switched Contact

•  IN  3     

Digital Input for Switched Contact

•  +12V    

Power from Controller

•  Comms 

Comms to Controller

•  GND   

Ground from Controller

Controller Terminal Identification

240 Volt Power connection to Control Unit:

• 

  

Earth

•  N 

 

Neutral supply

•  240V~  

Mains 240VAC Supply

Output Relays

•  NO   

Normally open contact

•  COM   

Common contact

Comms Terminals

•  +12V   

Power to Control Station

•  Comms 

Comms from Control Station

•  GND   

Ground to Control Station

Battery

Contains a lithium type battery, dispose of properly.

(In accordance with local regulations)

•  Type    

CR-2032 Lithium Battery

•  Nominal voltage  3 Volts

•  Shelf life  

5 years, dependent on ambient temperature

Caution: Risk of Explosion if battery is replaced by an incorrect type.

Temperature Ratings

•  Storage: 

0 to 50°C non-condensing

•  Operating: 

0 to 40°C non-condensing

•  Sensor Input: 

5 to 35°C

Models

:

M2K03: 

1 Speed FAN, 2 COOL and 2 HEAT Controller, 365 day   

 

Battery Backed Time Clock

DS 9.03 

October 2013

  

M2K03

Micro2000 Controller

Reviews: