background image

© MASS ELECTRONICS Pty Ltd  2008

Page 2
DS 9.03 - M2K03 - Micro2000 Controller
August 2013

Approvals

The

 Micro2000

 series controllers conform to:  

•  Electromagnetic emission and immunity requirements according 

to standards EN55011 (CISPR11) and EN50082 for CE Marking and 

C-Tick Labelling.

Installation

1. The

 Micro2000

 should be mounted on DIN rail in cabinets 

approved for switchgear or industrial control equipment. It 

should be mounted in a dry and clean location, free of excess 

vibration.  Maximum terminal cable entry is 1.5mm² wire.

2. Wire in accordance with INNOTECH connection diagrams and 

local bylaws or refer to your local distributor.

3. Connect the 240VAC supply to the correct terminals on the 

controller, observing the correct polarity of the connections.  

Connect the EARTH to the correct terminals on all units.

4. The maximum wire length between the control station and the 

controller should not exceed 50 metres.  The wiring between 

these devices should not be run in parallel with conductors 

carrying high current.

Fault Representation

1. If the Control Station display reads "HELP", this is due to a 

communications error between the Controller and the Control 

Station. Check the interconnecting 2 core screened cable 

for continuity or short circuits.  As a result of this failure the 

controller will shutdown after 1 minute.

2. If the Control Station reads "SEN FAIL", this is due to an open 

circuit room Temperature Detector. To test the detector, 

disconnect it from the room and connect it directly to the 

controller.

Inputs

1. INPUT 1 Temperature Sensor Input: (Range 5 - 35°C.)                   

This input is used to read the current temperature.

2. INPUT 2 - Selectable Dry Contact Digital Input:   

Using Parameter 14, Input 2 can be either be an AC Fault Input, 

a External Disable Input, or a Condenser Water Fault Input.

AC Fault

If "AC" is selected in Parameter 14 and Input 2 is "ON" the 

Micro2000 

will display "AC FAIL" and continue to operate in it's 

current mode.  After the fault is rectified, the display will revert 

back to its previous state.

External Disable

    

If "dIS" is selected in Parameter 14 and Input 2 is "ON" the 

Micro2000

 will shut down all outputs and display "OFF".  After 

the disable input is removed, the 

Micro2000

 will continue to 

operate in its previous state.

Condenser Water Fault

 

   

If "Con" is selected in Parameter 14 and Input 2 is "ON" the 

Micro2000

 will shut down all outputs except the Fan, display 

"Con FAIL".  After the fault is rectified, the 

Micro2000

 will 

continue to operate in its previous state. 

3. INPUT 3 - Selectable Dry Contact Digital Input:   

Using Parameter 15, Input 3 can be either an External  

 

After Hours Input, or a Door Switch Input. 

External Afterhours

 

   

If "AH" is selected in Parameter 15, Input 3 is used as an 

external toggle After Hours switch.  It operation is the same as 

the 

button on the front panel. See Push buttons section 

for more information.

Door Switch

 

If "Door" is selected in Parameter 15 and Input 3 is "ON" for the 

time set in Parameter 16 (Door Open Time), then the 

Micro2000

 will display "Door" and will go into Standby Mode.  In 

Standby mode the Dead Band is increased by the  

adjustable value in Parameter 17 (Door Reset Dead Band). If 

Parameter 17 reads 10°C, there is a 5°C dead band either side of 

the setpoint. However if Parameter 17 is set to 0 (Off) then the 

Micro2000

 will shutdown all outputs. After the door is closed the 

Micro2000

 will continue to operate in is previous state. 

All Digital Inputs have a 5 second delay before they are 

registered. Except the Condenser Water Fault which has a 20 

second delay. 

Outputs

Relay #1

Fan (16A Relay. Common and Normally Open  Contact)

Relay #2

Heat 1 (10A Relay. Common and Normally Open Contact)

Relay #3

Heat 2 (10A Relay. Common and Normally Open Contact)

Relay #4

Cool 2 (2A Relay. Common and Normally Open Contact)

Relay #5

Cool 1 (2A Relay. Common and Normally Open Contact)

Push Buttons

The normal control button use is described below:

1.  

 The "Auto" button is used to enable or disable the  

programmed  schedules.  When the Auto "LED" is on the  

schedules are enabled, when it is off they are disabled.

2.  

This button has three selectable modes of operation. 

Normal After Hours

 

 

   

 

If Parameter 6 (After Hours Adjustable) is set to "Off" , 

pressing the 

 button will instruct the Controller to run for 

the time set in Parameter 5 (After Hours Run Time). 

Adjustable After Hours Run Time

  

When the button is pressed and Parameter 6 is set to "On", the 

controller will display the amount of time in hours it will run for.  

The user can adjust this time by using the 

 and 

 buttons. 

The Controller will run for the amount of time chosen after the  

 button is pressed again or a period of 5 seconds where 

no buttons are pressed.

Manual Override

 

 

   

When Parameter 5 is set to "On", the 

 button can be used 

to change the current state of the controller. It can be used 

to override any programmed schedules. For example if the 

Controller has been turned on by a Schedule, the 

 button 

can be used to force the controller Off until the next scheduled 

"On" time. Similarly if the controller is Off, the 

 button 

can be used to force the controller On, until the next scheduled 

"Off" time. 

If the Schedules are disabled via the 

 button, the  

   

button has a normal On/Off function.

3.  

This button can be used to select either Vent mode (Fan 

only runs) or Condition Mode (Full control).

4.  

By pressing this button the Current Time will be  

displayed for 10 seconds before returning to the default  

display. If pressed again then the Current Date will be  

displayed for 10 seconds.

5.  

 

The Up and Down buttons can be used to change the 

current Setpoint.

This product should only be installed by qualified personnel.

Reviews: