DS 9.03 - M2K03 - Micro2000 Controller
August 2013

Parameters

Parameter 0: Sensor Calibration

The display will show the sensor temperature.  To offset the sensor 

temperature, adjust using the up and down buttons.

•  The range of offset is ± 10°C

•  The factory default setting is 0.0°C

Parameter 1: Minimum Setpoint 

The display will show the Minimum Setpoint to which the controller 

can be set.

•  The range of Minimum Setpoint is 5 to 35°C

•  The factory default setting is 15°C

Parameter 2: Maximum Setpoint 

The display will show the Maximum Setpoint to which the controller 

can be set.

•  The range of Maximum Setpoint is 5 to 35°C

•  The factory default setting is 30°C

Parameter 3: Dead Band 

The display will show the Dead Band setting.

•  The range of the Dead Band is 0 to 10.0°C

•  The factory default setting is 0.5°C

Parameter 4: Proportional Band 

The display will show the Proportional Band Setting. A Proportional 

Band setting of 2°C will result in a differential of 2°C for heating and 

2°C for cooling.

•  The range of Proportional Band is 0 to 10.0°C

•  The factory default setting is 1.0°C

Parameter 5: After Hours Timer 

The display will show the After Hours Time.  This is the period the 

unit will run for if an after hours pulse is received.

•  The range of the After Hours Time is 1 to 24 hours to 'On'

•  The factory default setting is 2 hours

Parameter 6: After Hours Adjustable 

The display will show the After Hours Adjustable setting.

•  On: After hours timer will be adjustable

•  Off: After hours timer will  use the value in Parameter 5

•  The factory default setting is Off

Parameter 7: Fan Run On Time 

The display will show the Fan Run On Time. This is the period the fan 

will run for if it is operating in heating and the controller is turned off.  

This is to remove any residual heat where electric heating is used.

•  The range of the Run On Time is 0 to 500 seconds

•  The factory default setting is 30 seconds

Parameter 8:  Compressor Minimum Off Time 

The display will show the Compressor Minimum Off Time.

This is the period the compressor must remain off before it can 

restart.

•  The range of the Off Time is 0 to 99 minutes

•  The factory default setting is 4 minutes

Parameter  9: EDH / REV 

The display will show either EDH or REV to select which mode the 

controller will operate.

•  Electric Heat mode (EDH): the heat and cool relays operate       

independently of each other.

•  Reverse Cycle mode (REV): the cool relay controls the compressor 

in both cooling and heating operations.  The heat relay operates 

the reversing valve.

•  The factory default setting is EDH.

Parameter 10: HEA / COOL 

The Display will show either HEA or COOL to select if the reversing 

valve is energised for cooling or energised for heating.

•  COOL: the heat relay will close during cooling

•  HEA:   the heat relay will close during heating

•  The factory default setting is HEA

This parameter is only effective if Parameter 9 is set for Reverse 

Cycle Operation.

Parameter 11: Fan Cycle 

The Display will show either On or Off to select continuous fan        

operation or fan cycles with heating.

•  On:  Fan cycles with heating

•  Off: Fan runs continuously

•  The factory default setting is Off

Parameter 12: Setpoint Display Only

The display will show either On or Off.

•  On: The setpoint is displayed

•  Off: The current temperature is displayed

•  The factory default setting is Off

Parameter 13: Daylight  Saving Enable

The display will show either On or Off.

•  On:  Daylight Saving is active

•  Off: Daylight Saving is not active

•  The factory default setting is Off

Parameter 14: Input 2 Function

The display will show the current function of input 2.

•  AC: AC Fault input

•  dIS: External Disable input

•  COn: Condenser Water Fault input

•  The factory default setting is AC

Parameter 15: Input 3 Function

The display will show the current function of input 3.

•  AH: External After Hours input

•  Door: Door Switch input 

•  The factory default setting is AH

Parameter 16: Door Open Time

The display will show the Door Open Time.

This is the period the Door must be open before it is registered.

•  The range of the Run On Time is 0 to 500 seconds

•  The factory default setting is 30

Parameter 17: Door Reset Dead Band

The display will show the Door Reset Dead Band Setting.

•  The range of the Dead Band is OFF to 10.0°C

•  See section 'Inputs' for more information

•  The factory default setting is OFF