background image

5

BEM/BEL SERIES

ENDLESS REMOTE GLASS DOOR MERCHANDISERS 

WITH BOTTOM MOUNTED COIL

REQUIRED CONDENSING UNITS

NO. OF 

DOORS

+35°F AVERAGE PRODUCT TEMP. 

+20°F SUCTION

75°F AIR CONDITIONED STORE

55% RELATIVE HUMIDITY

-3°F AVERAGE PRODUCT TEMP. 

-11°F SUCTION

75°F AIR CONDITIONED STORE

55% RELATIVE HUMIDITY

-12°F AVERAGE PRODUCT TEMP. 

-18°F SUCTION

75°F AIR CONDITIONED STORE

55% RELATIVE HUMIDITY

COND. UNIT REQUIRED FOR AIR 

TEMP. ENTERING CONDENSER*

COND. UNIT REQUIRED FOR AIR 

TEMP. ENTERING CONDENSER*

COND. UNIT REQUIRED FOR AIR 

TEMP. ENTERING CONDENSER*

90°F

100°F

110°F

90°F

100°F

110°F

90°F

100°F

110°F

2

MHHX0061B

MHHX0061B

MHHX0061B

MHLZ0071

MHLZ0071

MHLZ0071

MHLZ0091

MHLZ0091

MHLZ0091

3

MHHX0061B

MHHX0061B

MHHX0061B

MHLZ0071

MHLZ0091

MHLZ0091

MHLZ0091

MHLZ0121

MHLZ0121

4

MHHX0061B

MHHX0081B

MHHX0081B

MHLZ0091

MHLZ0091

MHLZ0121

MHLZ0121

MHLZ0121

MHLZ0121

5

MHHX0081B

MHHX0081B

MHHX0111

MHLZ0091

MHLZ0121

MHLZ0121

MHLZ0121

MCLZ0141

MCLZ0171

6

MHHX0111

MHHX0111

MHHX0111

MHLZ0121

MHLZ0121

MCLZ0141

MCLZ0141

MCLZ0171

MDLZ0201

7

MHHX0111

MHHX0111

MHHX0151

MHLZ0121

MCLZ0141

MCLZ0171

MCLZ0171

MDLZ0201

MDLZ0201

8

MHHX0151

MHHX0151

MHHX0151

MCLZ0141

MCLZ0171

MCLZ0171

MDLZ0201

MDLZ0201

MDLZ0231

9

MHHX0151

MHHX0151

MHHX0191

MCLZ0171

MCLZ0171

MDLZ0201

MDLZ0231

MDLZ0231

MDLZ0291

10

MHHX0151

MHHX0191

MHHX0191

MCLZ0171

MDLZ0201

MDLZ0231

MDLZ0231

MDLZ0291

MDLZ0291

11

MHHX0191

MHHX0191

MHHX0221

MDLZ0201

MDLZ0231

MDLZ0231

MDLZ0291

MDLZ0291

MDLZ0331

12

MHHX0191

MHHX0221

MHHX0221

MDLZ0231

MDLZ0231

MDLZ0291

MDLZ0291

MDLZ0291

MDLZ0331

13

MHHX0191

MHHX0221

MHHX0251

MDLZ0231

MDLZ0291

MDLZ0291

MDLZ0291

MDLZ0331

BCLZ0750

14

MHHX0221

MHHX0251

MHHX0251

MDLZ0291

MDLZ0291

MDLZ0291

MDLZ0331

BCLZ0750

BCLZ1000

15

MHHX0251

MHHX0251

MHHX0301

MDLZ0291

MDLZ0291

MDLZ0331

BCLZ0750

BCLZ0750

BCLZ1000

16

MHHX0251

MHHX0251

MHHX0301

MDLZ0291

MDLZ0331

BCLZ0750

BCLZ0750

BCLZ1000

BCLZ1000

17

MHHX0251

MHHX0301

MHHX0351

MDLZ0291

MDLZ0331

BCLZ0750

BCLZ1000

BCLZ1000

BCLZ1000

18

MHHX0301

MHHX0301

MHHX0351

MDLZ0331

BCLZ0750

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

19

MHHX0301

MHHX0351

MHHX0351

BCLZ0750

BCLZ0750

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

20

MHHX0301

MHHX0351

MHHX0441

BCLZ0750

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

21

MHHX0351

MHHX0351

MHHX0441

BCLZ0750

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

22

MHHX0351

MHHX0441

MHHX0441

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

BCLZ1500

23

MHHX0351

MHHX0441

MHHX0441

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

BCLZ1500

24

MHHX0441

MHHX0441

MHHX0441

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

BCLZ1500

BCLZ1500

25

MHHX0441

MHHX0441

MHHX0501

BCLZ1000

BCLZ1000

BCLZ1000

BCLZ1500

BCLZ1500

BCLZ1500

*Condensing unit and line size based on 100' line run.

See the Master-Bilt 

Condensing Unit & Refrigeration Systems I/O Manual

 for other conditions.

For other than high capacity condensing units, consult factory. 

Use this chart to determine the correct condensing unit for your endless lineup. 
Unless already indicated, add suffix "B" for one phase or "C" for three phase model.

Reviews: