background image

 

3/15   Rev. C   157872 

 

 

INTRODUCTION 

 
Thank you for purchasing this

 

cabinet.  This manual contains important instructions for installing, using and servicing 

an  Open Air Merchandiser.  Read all these documents carefully before installing or servicing your equipment.  This 
manual should be left in the care of the store owner or manager. 
 

 

STORE CONDITIONS / LOCATION 

 
The  OAM  cases are designed to operate in the controlled environment of an air conditioned store.  The store 
temperature should be at or below +75

°

F and a relative humidity of 55% or less.  At higher temperature or humidity 

conditions, the performance of these cases may be affected and the capacity diminished.  It is not uncommon in a 
newly constructed store for the temperature and humidity to be above design conditions.  These excessive conditions 
may produce sweating in the case until the store is operational and the ambient environment is more desirable.  
 
The  OAM  case  should not be positioned where it is directly exposed to rays of the sun or near a direct source of 
radiant heat or air flow. No HVAC return or supply air ducts may be located near case openings.  This will adversely 
affect the case air flow and will result in poor performance.  Do not open windows or doors that will affect the case air 
flow.  The maximum air velocity near the case air return is 50 FPM.  If this case is to be located against a wall there 
should be at least a  6” space between the wall and the back of the case. The cabinet also requires a clearance of 10” 
at the top.  This space will allow for the circulation of air behind the case.  

 

These cases should always be loaded properly.  This unit will operate differently when loaded or unloaded.  Consult the 
section of this manual that specifies loading procedures. 
 
A pipe loop acts as a trap  is included with each case.  It is important that each case has this installed.  Consult the 
section of this manual for installing and piping the drain. 
 

 

NOTICE 

 

Read this manual before installing your cabinet.  Keep the manual and refer to it before 

doing any service on the equipment.  Failure to do so could result in personal injury or damage to the cabinet. 

 

DANGER

 

 

Improper or faulty hook-up of electrical components of the refrigeration units can result in 

severe injury or death.  All electrical wiring hook-ups must be done in accordance with all applicable local, 
regional or national standards. 

 

 

NOTICE

 

 

Installation and service of the refrigeration and electrical components of the cabinet must be performed by a 
refrigeration mechanic and/or a licensed electrician.

 

 
The portion of this manual covering refrigeration and electrical components contain technical instructions intended only 
for persons qualified to perform refrigeration and electrical work. 
This manual cannot cover every installation, use or service situation.  If you need additional information, call or write 
our Customer Service Department. 
 

 

 

 

Summary of Contents for HOAM 36

Page 1: ...ons 4 Thermometer Installation 4 Shelf and Shelf Lighting Installation 4 8 Plumbing 9 ELECTRICAL 10 STARTING PROCEDURE 10 FINAL CHECK LIST 10 LOADING 11 PLACING PRODUCT IN CABINET 11 CLEANING 11 ELECT...

Page 2: ...is to be located against a wall there should be at least a 6 space between the wall and the back of the case The cabinet also requires a clearance of 10 at the top This space will allow for the circu...

Page 3: ...eration or service information If you ignore the message you may damage your cabinet The warning and safety labels shown throughout this manual are placed on your Nor Lake Products cabinet at the fact...

Page 4: ...or at least 2 hours after it is started 5 Stock cases as quickly as possible exposing only small quantities to store temperatures for short periods of time 6 When replacing burned out LED light bars b...

Page 5: ...nd cable as shown in the image below If this is not a lighted shelf assembly skip this step and proceed to the next step 2 With shelf top turned upside down position shelf brace midway inside shelf to...

Page 6: ...arrow in the image so the bracket will snap under shelf top while also manuevering the shelf brace so it fits in the notch of the shelf bracket as the shelf bracket is being lowered into the shelf top...

Page 7: ...ves can be positioned to stock products horizontally or at an angle To position the shelves horizontally use the notches indicated on the shelf bracket at the desired level using the spaces available...

Page 8: ...d level using the spaces available on the pilasters Make sure the corresponding pilaster slots are used on both sides to make sure shelves are level Use the inside notches on shelf bracket to position...

Page 9: ...from refrigeration area 2 Remove drain hose from loop inside condensate pan DO NOT REMOVE LOOP and discard 3 Remove condensate power cord from refrigeration area and route thru bushing where drain hos...

Page 10: ...ast once FINAL CHECK LIST A Check that the evaporator drain line is properly connected B All shelves are properly installed C All LED light bars are properly secure to the bottom of the shelf and plug...

Page 11: ...interfere with the air flow of the case and will result in diminished performance PLACING PRODUCT IN THE CABINET Do not load the cabinet with product to the point that the air discharge grille air int...

Page 12: ...The COMP indicator will be off Fan The fans will run constantly during cool mode and defrost mode When the evaporator temp is above 55 o F the FAN will be off Defrost The control uses time defrost wit...

Page 13: ...hr 0 24 6 day DLI Defrost Termination Temperature 50 120 40 F DTO Maximum Defrost Duration 1 120min 10 min ELECTRICAL CONNECTIONS The controller is provided with screw push terminal block to connect c...

Page 14: ...17 10 50 17 643 17 926 18 210 15 59 14 472 14 674 14 877 20 68 11 938 12 081 12 224 25 77 9 900 10 000 10 100 30 86 8 217 8 315 8 413 35 95 6 854 6 948 7 043 40 104 5 745 5 834 5 923 45 113 4 834 4 91...

Page 15: ...ked with frost or ice A Defective temperature control B Defective or disconnected coil sensor C Improper control setting D Ambient conditions above 75 F E Pipe loop acts as a trap in drain not install...

Page 16: ...3 155743 Evaporator Coil 159279 159280 159281 159282 Evaporator Fan Blade 159283 159283 159283 159283 Evaporator Fan Motor 155726 155726 155726 155726 Electronic Controller 155746 155746 155746 155746...

Page 17: ...3 155743 Evaporator Coil 159279 159280 159281 159282 Evaporator Fan Blade 159283 159283 159283 159283 Evaporator Fan Motor 155726 155726 155726 155726 Electronic Controller 155746 155746 155746 155746...

Page 18: ...3 155743 Evaporator Coil 159279 159280 159281 159282 Evaporator Fan Blade 159283 159283 159283 159283 Evaporator Fan Motor 155726 159726 159726 155726 Electronic Controller 155746 155746 155746 155746...

Page 19: ...43 Evaporator Coil 159278 159284 159285 159286 Evaporator Fan Blade 155740 155740 155740 155740 Evaporator Fan Motor 155726 155726 155726 155726 Electronic Controller 155746 155746 155746 155746 Box S...

Page 20: ...41 159141 Casters 2 Diameter 143678 143678 143678 143678 Product Hooks Retractable Night Cover Sandwich Display Hooks Security Cover Description VOAM 36 79 VOAM 48 79 VOAM 60 79 VOAM 72 79 Shelf Assem...

Page 21: ...21 3 15 Rev C 157872 DESCRIPTION DATE MODEL S DRAWN BY VERTICAL HORIZONTAL OPEN AIR MERCHANDISERS 115V LAE AT2 CONTROL BGH 4 7 14...

Page 22: ...22 3 15 Rev C 157872 DESCRIPTION DATE MODEL S DRAWN BY VERTICAL HORIZONTAL OPEN AIR MERCHANDISERS REMOTE 115V LAE AT2 CONTROL BGH 5 2 14...

Page 23: ...23 3 15 Rev C 157872 DESCRIPTION DATE MODEL S DRAWN BY VERTICAL ONLY OPEN AIR MERCHANDISERS 220V LAE AT2 CONTROL BGH 4 7 14...

Page 24: ...24 3 15 Rev C 157872 DESCRIPTION DATE MODEL S DRAWN BY VERTICAL HORIZONTAL OPEN AIR MERCHANDISERS CANADA CABINETS ONLY 115V LAE AT2 CONTROL BGH 7 16 14...

Reviews: