PLUMBING
Each OAM case has an optional electric, heated condensate pan and a looped drain hose connecting the drain to the
outside of the case. It is very important that this loop not be removed as it will result in diminished peformance of the
case without it. End user should plumb drain hose to floor drain. Please observe the following:
1. Always install drains in accordance with local codes.
2. Use largest possible size pipe for drains, ½” ID minimum is recommended.
3. Provide as much downhill slope as possible.
4. Prevent drains from freezing. Do not install drains in contact with uninsulated suction lines.
If it is preferred to use the
heated condensate pan:
1. Remove rear guard from refrigeration area.
2. Remove drain hose from loop inside condensate pan (DO NOT REMOVE LOOP) and discard
3. Remove condensate power cord from refrigeration area, and route thru bushing where drain hose was.
4. Re-install rear guard, connect condensate vaporizer cord to dedicated 115v outlet.
NOTICE TO STORE OWNERS / MANAGERS
Moisture or liquid around or under the cabinet is a potential slip/fall hazard for persons walking by or working
in the general area of the cabinet. Any cabinet malfunction or housekeeping problem that creates a slip/fall
hazard around or under the cabinet should be corrected immediately.
-
If moisture or liquid is observed around or under a cabinet, an immediate investigation should be made by
qualified personnel to determine the source of the moisture or liquid. The investigation made should determine
if the cabinet is malfunctioning or if there is a drain pipe leaking.